5-58
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
c) NEUTRAL INSTANTANEOUS OVERCURRENT
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
NEUTRAL OC
ÖØ
W1(3) NTRL INST OC 1(2)
•
W1(3) NEUTRAL INST OC 1(2) PICKUP
: Enter the level of neutral current (in units of relay nominal current) above
which the Winding 1(3) Neutral Instantaneous Overcurrent 1 element will pickup and start the delay timer.
•
W1(3) NEUTRAL INST OC 1(2) DELAY
: Enter the time that the neutral current must remain above the pickup level
before the element operates.
The setpoint messages above and the following logic diagram are identical for the Neutral Instantaneous
Overcurrent 2 element.
Figure 5–18: NEUTRAL IOC 1 SCHEME LOGIC
W1 NTRL INST OC 1
[ENTER] for more
W1 NEUTRAL INST OC 1
FUNCTION: Enabled
Range: Enabled, Disabled
W1 NEUTRAL INST OC 1
TARGET: Latched
Range: Self-Reset, Latched, None
W1 NEUTRAL INST OC 1
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 x CT in steps of 0.01
W1 NEUTRAL INST OC 1
DELAY: 0 ms
Range: 0 to 60000 ms in steps of 1
W1 NEUTRAL INST OC 1
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
NOTE