GE Multilin
745 Transformer Management Relay
7-45
7 COMMUNICATIONS
7.4 MODBUS MEMORY MAP
7
WINDING 3
HARMONIC
DERATING
2366
Reserved
↓
↓
↓
↓
↓
↓
↓
236F
Reserved
2370
Winding 3 Harm Derating Function
---
---
---
F30
0 = Disabled
2371
Winding 3 Harm Derating Target
---
---
---
F46
0 = Self-reset
2372
Winding 3 Harm Derating Min. Operating Current
0.03 to 1.00
0.01
×
CT
F3
10 = 0.10
×
CT
2373
Winding 3 Harm Derating Pickup
0.01 to 0.98
0.01
---
F3
90 = 0.90
2374
Winding 3 Harm Derating Delay
0 to 60000
1
s
F1
10 s
2375
Winding 3 Harm Derating Block
---
---
---
F87
0 = Disabled
2376
Reserved
↓
↓
↓
↓
↓
↓
↓
237F
Reserved
HOTTEST-
SPOT LIMIT
2380
Hottest-spot Limit Function
---
---
---
F30
0 = Disabled
2381
Hottest-spot Limit Target
---
---
---
F46
0 = Self-reset
2382
Hottest-spot Limit Pickup
50 to 300
1
° C
F1
150° C
2383
Hottest-spot Limit Delay
0 to 60000
1
min
F1
10 min
2384
Hottest-spot Limit Block
---
---
---
F87
0 = Disabled
2385
Reserved
↓
↓
↓
↓
↓
↓
↓
238F
Reserved
LOSS-OF-LIFE
LIMIT
2390
Loss-of-Life Limit Function
---
---
---
F30
0 = Disabled
2391
Loss-of-Life Limit Target
---
---
---
F46
0 = Self-reset
2392
Loss-of-Life Limit Pickup
0 to 20000
1
hrs x 10
F1
16000=160000 hrs
2393
Loss-of-Life Limit Block
---
---
---
F87
0 = Disabled
2394
Reserved
↓
↓
↓
↓
↓
↓
↓
239F
Reserved
ANALOG
INPUT
LEVEL 1
23A0
Analog Input Level 1 Function
---
---
---
F30
0 = Disabled
23A1
Analog Input Level 1 Target
---
---
---
F46
0 = Self-reset
23A2
Analog Input Level 1 Pickup
1 to 65000
1
<Units>
F1
10 <Units>
23A3
Analog Input Level 1 Delay
0 to 60000
1
s
F1
50 s
23A4
Analog Input Level 1 Block
---
---
---
F87
0 = Disabled
23A5
Reserved
↓
↓
↓
↓
↓
↓
↓
23AF
Reserved
ANALOG
INPUT
LEVEL 2
23B0
Analog Input Level 2 Function
---
---
---
F30
0 = Disabled
23B1
Analog Input Level 2 Target
---
---
---
F46
0 = Self-reset
23B2
Analog Input Level 2 Pickup
1 to 65000
1
<Units>
F1
100 <Units>
23B3
Analog Input Level 2 Delay
0 to 60000
1
s
F1
100 s
23B4
Analog Input Level 2 Block
---
---
---
F87
0 = Disabled
23B5
Reserved
↓
↓
↓
↓
↓
↓
↓
23BF
Reserved
WINDING 1
CURRENT
DEMAND
23C0
Winding 1 Current Demand Function
---
---
---
F30
0 = Disabled
23C1
Winding 1 Current Demand Target
---
---
---
F46
0 = Self-reset
23C2
Winding 1 Current Demand Pickup
---
---
A
F78
100 A
23C3
Winding 1 Current Demand Block
---
---
---
F87
0 = Disabled
23C4
Reserved
↓
↓
↓
↓
↓
↓
↓
23CF
Reserved
WINDING 2
CURRENT
DEMAND
23D0
Winding 2 Current Demand Function
---
---
---
F30
0 = Disabled
23D1
Winding 2 Current Demand Target
---
---
---
F46
0 = Self-reset
23D2
Winding 2 Current Demand Pickup
---
---
A
F79
400 A
23D3
Winding 2 Current Demand Block
---
---
---
F87
0 = Disabled
Table 7–5: 745 MEMORY MAP (Sheet 33 of 35)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT