GE Multilin
745 Transformer Management Relay
5-35
5 SETPOINTS
5.4 S2 SYSTEM SETUP
5
5.4.9 ANALOG INPUT
PATH: SETPOINTS
ÖØ
S2 SYSTEM SETUP
ÖØ
ANALOG INPUT
The 745 provides a general purpose DC current input for use in monitoring any external parameter. Any standard trans-
ducer output may be connected to the analog input for monitoring.
•
ANALOG INPUT NAME
: Press
to begin editing the name of the analog input. The text may be changed from
"Analog Input" one character at a time, using the
/
keys. Press the
key to store the edit and
advance to the next character position. This name will appear in the actual value message
A2 METERING
ÖØ
ANALOG
INPUT
.
•
ANALOG INPUT UNITS
: Enter the units of the quantity being read by editing the text as described above. The 6 char-
acters entered will be displayed instead of Units wherever the analog input units are displayed.
•
ANALOG INPUT RANGE
: Select the current output range of the transducer that is connected to the analog input.
•
ANALOG INPUT MINIMUM/MAXIMUM
: Enter the value of the quantity measured which corresponds to the minimum/
maximum output value of the transducer.
ANALOG INPUT
[ENTER] for more
ANALOG INPUT NAME:
Analog Input
Range: 18 alphanumeric characters
ANALOG INPUT UNITS:
µ
A
Range: 6 alphanumeric characters
ANALOG INPUT RANGE:
0-1 mA
Range: 0-1 mA, 0-5 mA, 4-20 mA, 0-20 mA.
ANALOG INPUT MINIMUM
VALUE: 0
µ
A
Range: 0 to 65000 in steps of 1. The units are chosen by
ANALOG INPUT UNITS
setpoint
ANALOG INPUT MAXIMUM
VALUE: 1000
µ
A
Range: 0 to 65000 in steps of 1. The units are chosen by
ANALOG INPUT UNITS
setpoint
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
VALUE
VALUE
ENTER