5-60
745 Transformer Management Relay
GE Multilin
5.6 S4 ELEMENTS
5 SETPOINTS
5
b) GROUND TIME OVERCURRENT
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
GROUND OC
Ö
W1(3) GND TIME OC
•
W1(3) GROUND TIME OC PICKUP
: Enter the level of ground current (in units of relay nominal current) above which
the Winding 1(3) Ground Time Overcurrent element will pickup and start timing.
•
W1(3) GROUND TIME OC SHAPE
: Select the time overcurrent curve shape to be used for the Winding 1(3) Ground
Time Overcurrent element. Refer to Time Overcurrent Curves on page 5–49 for a description of the time overcurrent
curve shapes.
•
W1(3) GROUND TIME OC MULTIPLIER
: Enter the multiplier constant by which the selected time overcurrent curve
shape (the base curve) is to be shifted in time.
•
W1(3) GROUND TIME OC RESET
: Enter the multiplier constant by which the selected time overcurrent curve shape
(the base curve) is to be shifted in time.
Figure 5–19: GROUND TOC SCHEME LOGIC
W1 GND TIME OC
[ENTER] for more
W1 GROUND TIME OC
FUNCTION: Enabled
Range: Enabled, Disabled
W1 GROUND TIME OC
TARGET: Latched
Range: Self-Reset, Latched, None
W1 GROUND TIME OC
PICKUP: 0.85 x CT
Range: 0.05 to 20.00 x CT in steps of 0.01
W1 GROUND TIME OC
SHAPE: Ext Inverse
Range: see description below
W1 GROUND TIME OC
MULTIPLIER: 1.00
Range: 0.00 to 100.00 in steps of 0.01
W1 GROUND TIME OC
RESET: Linear
Range: Instantaneous, Linear
W1 GROUND TIME OC
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE