745 Transformer Management Relay
GE Multilin
5.2 AUTO-CONFIGURATION
5 SETPOINTS
5
D/d0°/d0°
1
DELTA
0°
2
DELTA
0°
0°
3
DELTA
0°
0°
D/d0°/d60°
1
DELTA
60° lag
2
DELTA
0°
60° lag
3
DELTA
60° lag
0°
D/d0°/d120°
1
DELTA
120° lag
2
DELTA
0°
120° lag
3
DELTA
120° lag
0°
D/d0°/d180°
1
DELTA
180° lag
2
DELTA
0°
180° lag
3
DELTA
180° lag
0°
D/d0°/d240°
1
DELTA
240° lag
2
DELTA
0°
240° lag
3
DELTA
240° lag
0°
Table 5–1: TRANSFORMER TYPES (SHEET 13 OF 24)
TRANSFORMER
TYPE
WDG # CONNECTION
VOLTAGE
PHASORS
PHASE
SHIFT
D/d0°/d300°
1
DELTA
300° lag
2
DELTA
0°
300° lag
3
DELTA
300° lag
0°
D/d0°/y30°
1
DELTA
0°
2
DELTA
0°
0°
3
WYE
(gnd 2/3)
30° lag
330° lag
D/d0°/y150°
1
DELTA
0°
2
DELTA
0°
0°
3
WYE
(gnd 2/3)
150° lag
210° lag
D/d0°/y210°
1
DELTA
0°
2
DELTA
0°
0°
3
WYE
(gnd 2/3)
210° lag
150° lag
D/d0°/y330°
1
DELTA
0°
2
DELTA
0°
0°
3
WYE
(gnd 2/3)
330° lag
30° lag
Table 5–1: TRANSFORMER TYPES (SHEET 14 OF 24)
TRANSFORMER
TYPE
WDG # CONNECTION
VOLTAGE
PHASORS
PHASE
SHIFT