GE Multilin
745 Transformer Management Relay
5-85
5 SETPOINTS
5.6 S4 ELEMENTS
5
5.6.15 CURRENT DEMAND
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
CURRENT DEMAND
Ö
W1 CURRENT DEMAND
This section contains the settings to configure the current demand monitoring elements. Included are a current demand
level for each winding and each phase.
Figure 5–40: CURRENT DEMAND SCHEME LOGIC
W1 CURRENT DEMAND
[ENTER] for more
W1 CURRENT DEMAND
FUNCTION: Disabled
Range: Enabled, Disabled
W1 CURRENT DEMAND
TARGET: Self-Reset
Range: Self-Reset, Latched, None
W1 CURRENT DEMAND
PICKUP: 100 A
Range: 0 to 65000 in steps of 1 (auto-ranging)
W1 CURRENT DEMAND
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE