GE Multilin
745 Transformer Management Relay
1-5
1 PRODUCT OVERVIEW
1.2 SPECIFICATIONS
1
1.2.3 PROTECTION ELEMENTS
PERCENT DIFFERENTIAL
Operating Current Pkp: 0.05 to 1.00
×
CT in steps of 0.01
Dropout Level:
97 to 98% of Pickup
SLOPE-1 Range:
15% to 100% in steps of 1
SLOPE-2 Range:
50% to 100% in steps of 1
KP (Slope-1 Kneepoint): 1.0 to 20.0
×
CT in steps of 0.1
Harmonic Restraint:
0.1% to 65.0% in steps of 0.1
Solid State Output Operate Time:
at Pickup < 1
×
CT: 42 to 52 ms
at 1
×
CT < Pickup < 1.1
×
kneepoint: 34 to 44 ms
at Pickup > 1.1
×
kneepoint: 26 to 36 ms
Relay Outputs 2 to 5 Operate Time:
at Pickup < 1
×
CT: 46 to 56 ms
at 1
×
CT < Pickup < 1.1
×
kneepoint: 38 to 48 ms
at Pickup > 1.1
×
kneepoint: 30 to 40 ms
INSTANTANEOUS DIFFERENTIAL OVERCURRENT
Pickup Level:
3.00 to 20.00
×
CT in steps of 0.01
Dropout Level:
97 to 98% of Pickup
Level Accuracy:
Per current input
Solid State Output Operate Time:
at 1.2
×
pickup:
22 to 30 ms
at 2.0
×
pickup:
18 to 26 ms
at 4.0
×
pickup:
11 to 19 ms
Relay Outputs 2 to 5 Operate Time:
at 1.2
×
pickup:
28 to 36 ms
at 2.0
×
pickup:
24 to 32 ms
at 4.0
×
pickup:
17 to 25 ms
PHASE / NEUTRAL / GROUND / NEGATIVE SEQUENCE
TIME OVERCURRENT
Pickup Level:
0.05 to 20.00
×
CT in steps of 0.01
Dropout Level:
97 to 98% of Pickup
Curve Shapes:
ANSI Extremely/Very/Moderately/Nor-
mally Inverse; Definite Time (0.1 s base
curve); IEC Curve A/B/C and Short;
FlexCurve™ A/B/C (programmable
curves); IAC Extreme/Very/Inverse/Short
Curve Multiplier:
0.5 to 30 for ANSI, IAC, and Flex-
Curves™ in steps of 0.1 s; 0.05 to
100.00 for IEC curves in steps of 0.01
Reset Type:
Instantaneous or Linear
Level Accuracy:
Per current input
Timing Accuracy:
±3% of trip time or ±20 ms (whichever is
greater) at
≥
1.03
×
pickup
PHASE / NEUTRAL / GROUND / NEGATIVE SEQUENCE
INSTANTANEOUS OVERCURRENT
Pickup Level:
0.05 to 20.00
×
CT in steps of 0.01
Dropout Level:
97 to 98% of Pickup
Time Delay:
0 to 60000 ms in steps of 1
Level Accuracy:
Per current input
Solid State Output Operate Time:
at 1.2
×
pickup:
22 to 30 ms
at 2.0
×
pickup:
18 to 26 ms
at 4.0
×
pickup:
11 to 19 ms
Relay Outputs 2 to 5 Operate Time
at 1.2
×
pickup:
28 to 36 ms
at 2.0
×
pickup:
24 to 32 ms
at 4.0
×
pickup:
17 to 25 ms
RESTRICTED GROUND FAULT
Number of Elements:
2
Minimum Pickup:
0.02 to 20.00
×
CT in steps of 0.01
Dropout Level:
97 to 98% of Pickup
Slope Range:
0 to 100% in steps of 1
Pickup Delay:
0.00 to 600.00 s in steps of 0.01
Operating time:
at 1.1
×
pickup: 30 to 40 ms
at 10
×
pickup: 20 to 30 ms
UNDERFREQUENCY
Number of Elements:
2
Operating Current Pkp: 0.05 to 1.00
×
CT in steps of 0.01
Operating Voltage Pkp
0.10 to 0.99
×
VT in steps of 0.01
Pickup Level:
45.00 to 59.99 Hz in steps of 0.01
Dropout Level:
0.03 Hz
Time Delay:
0.00 to 600.00 s in steps of 0.01
Signal Source:
Winding 1 Phase A current / voltage
Level Accuracy:
±0.02 Hz
Solid State Output Operate Time:
at 3% beyond pickup: 120 to 150 ms
Relay Outputs 2 to 5 Operate Time:
at 3% beyond pickup: 125 to 155 ms (delay set at 0.0 s)
FREQUENCY RATE OF CHANGE
Number of Elements:
4
Operating Current Pkp: 0.05 to 1.00
×
CT in steps of 0.01
Operating Voltage Pkp
0.10 to 0.99
×
VT in steps of 0.01
Pickup Level:
45.00 to 59.99 Hz in steps of 0.01
Dropout Level:
0.03 Hz
Rate 1/2/3/4:
0.1 to 5.0 Hz/sec. in steps of 0.1
Dropout Level:
0.07 Hz/sec.
Signal Source:
Winding 1 Phase A current / voltage
Level Accuracy:
±0.02 Hz
Operate Time:
The operate time of the frequency trend
element is variable and is dependent on
the decay rate setting and the supervi-
sion frequency level.