GE Multilin
745 Transformer Management Relay
5-31
5 SETPOINTS
5.4 S2 SYSTEM SETUP
5
5.4.3 WINDING
PATH: SETPOINTS
ÖØ
S2 SYSTEM SETUP
ÖØ
WINDING 1(3)
These setpoints describe the characteristics of each transformer winding and the CTs connected to them.
The above setpoint options are also available for the second and third winding. Winding 3 setpoints are only visible
if the unit has the appropriate hardware and if the selected
TRANSFORMER TYPE
is 3-winding transformer.
•
WINDING 1(3) NOM
Φ
-
Φ
VOLTAGE
: Enter the nominal phase-to-phase voltage rating of Winding 1(3) of the trans-
former. The range for this setpoint is affected by the
S2 SYSTEM SETUP
Ö
TRANSFORMER
ÖØ
LOW VOLTAGE WINDING
RATING
setting (see table below).
•
WINDING 1(3) RATED LOAD
: Enter the self-cooled load rating for Winding 1(3) of the transformer. The range for this
setpoint is affected by the
S2 SYSTEM SETUP
Ö
TRANSFORMER
ÖØ
LOW VOLTAGE WINDING RATING
setting (see the table
below).
•
WINDING 1(3) PHASE CT PRIMARY
: Enter the phase CT primary current rating of the current transformers con-
nected to Winding 1(3). The CT secondary current rating must match the relay phase current input rating indicated.
•
WINDING 1(3) GROUND CT PRIMARY
: Enter the ground CT primary current rating of the current transformers con-
nected in the Winding 1(3) neutral to ground path. The CT secondary current rating must match the relay ground cur-
rent input rating indicated. This message will only appear if the transformer type setpoint shows that Winding 1(3) is a
wye-connected winding.
•
WINDING 1(3) SERIES 3-
Φ
RESISTANCE
: Enter the series three-phase resistance of the winding (that is, the sum of
the resistance of each of the three phases for the winding). This value is normally only available from the transformer
manufacturer’s test report, and is used in the 745 for calculation of harmonic derating factor.
WINDING 1
[ENTER] for more
WINDING 1 NOM
Φ
-
Φ
VOLTAGE: 220.0 kV
Range: Dependent on
LOW VOLTAGE WINDING RATING
setpoint; see description below.
WINDING 1 RATED
LOAD: 100.0 MVA
Range: Dependent on
LOW VOLTAGE WINDING RATING
setpoint; see description below.
WINDING 1 PHASE CT
PRIMARY: 500:5 A
Range: 1 to 50000:5 A in steps of 1
WINDING 1 GROUND CT
PRIMARY: 500:5 A
Range: 1 to 50000:5 A in steps of 1
WINDING 1 SERIES 3
Φ
RESISTANCE: 10.700
Ω
Range: 0.001 to 50.000
Ω
in steps of 0.001
SETTING (
X
= 1, 2, 3)
LOW VOLTAGE WINDING RATING VALUE
ABOVE 5 KV
1 KV TO 5 KV
BELOW 1 KV
WINDING
X
NOM
Φ
-
Φ
VOLTAGE
0.1 to 2000.0
in steps of 0.1 kV
0.01 to 200.00
in steps of 0.01 kV
0.001 to 20.000
in steps of 0.001 kV
WINDING
X
RATED LOAD
0.1 to 2000.0
in steps of 0.1 MVA
0.01 to 200.00
in steps of 0.01 MVA
0.001 to 20.000
in steps of 0.001 MVA
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
NOTE