2–30
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
40889
0378
Aux U/V Alarm Delay
1
60
1
s
F1
5
1
40890
0379
Aux UV Trip
60
91
1
eUnitNCV F1
*
91
1
40891
037A
Aux UV Trip Delay
1
60
1
s
F1
5
1
40892
037B
Reserved
---
---
---
---
---
---
1
40893
037C
Reserved
---
---
---
---
---
---
1
40894
037D
Reserved
---
---
---
---
---
---
1
PHASE OVERVOLTAGE (REQUIRED=IO_B)
40895
037E
Overvoltage Alarm Level
101
121
1
%MNV
F1
*
121
1
40896
037F
Overvoltage Alarm Delay
1
60
1
s
F1
30
1
40897
0380
Overvoltage Trip Level
101
121
1
%MNV
F1
*
121
1
40898
0381
Overvoltage Trip Delay
1
60
1
s
F1
30
1
40899
0382
Reserved
---
---
---
---
---
---
1
40900
0383
Reserved
---
---
---
---
---
---
1
40901
0384
Reserved
---
---
---
---
---
---
1
40902
0385
Reserved
---
---
---
---
---
---
1
PHASE REVERSAL (REQUIRED=IO_B)
40903
0386
Voltage Phase Reversal
0
2
1
---
FC140
1
1
40904
0387
Reserved
---
---
---
---
---
---
1
40905
0388
Reserved
---
---
---
---
---
---
1
40906
0389
Reserved
---
---
---
---
---
---
1
40907
038A
Reserved
---
---
---
---
---
---
1
VT FUSE FAIL (REQUIRED=IO_B)
40908
038B
VT Fuse Fail
0
2
1
---
FC140
0
1
40909
038C
Reserved
---
---
---
---
---
---
1
40910
038D
Reserved
---
---
---
---
---
---
1
40911
038E
Reserved
---
---
---
---
---
---
1
MAINTENANCE
40912
038F
Drive Greasing Interval
100
50100
100
hrs
F1
*
50100
1
40913
0390
Contactor Inspection Interval
100
65000
100
ops
F1
*
65000
1
40914
0391
Max Motor Stopped Time
10
10010
10
hrs
F1
*
10010
1
40915
0392
Reserved
---
---
---
---
---
---
1
40916
0393
Reserved
---
---
---
---
---
---
1
START INHIBIT
40917
0394
Start Inhibit Margin
0
11
1
%
F1
*
11
1
40918
0395
Reserved
---
---
---
---
---
---
1
40919
0396
Starts/Hour Limit
1
6
1
F1
*
6
1
40920
0397
Time Between Starts
1
3601
1
s
F1
*
3601
1
40921
0398
Reserved
---
---
---
---
---
---
1
CHANGE MODE
40922
0399
Change Mode on Comm Alarm 0
1
1
---
FC126
0
1
40923
039A
Change Mode when running
0
1
1
---
FC126
0
1
40924
039B
Reserved
---
---
---
---
---
---
1
40925
039C
Reserved
---
---
---
---
---
---
1
RESTART BLOCK
40926
039D
Restart Block Time
1
50001
1
s
F1
*
50001
1
40927
039E
Reserved
---
---
---
---
---
---
1
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in
Words