CHAPTER 4: FIELDBUS INTERFACE
DEVICENET PROTOCOL
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
4–67
0D
Starter Type
None
FC139
0
7
0
2
0E
Motor FLA
Amps
F2B
5
10001
10001
2
0F
High Speed FLA
Amps
F2B
5
10001
10001
2
10
Motor Name Plate Voltage Volts
F1
100 690
690
2
11
Change Over Current
FLA
F2B
10 51
15
2
12
Transfer Time
Seconds
F1
0
125
1
2
13
High Speed Start Block
None
FC126
0
1
1
2
14
Ramp Up Time
Seconds
F1
0
125
1
2
15
Ramp Down Time
Seconds
F1
0
125
1
2
16
Precontactor Time
Seconds
F1
0
60
0
2
17
Motor Rating
Kw
F2B
3
11001
11001
2
18
High Speed Motor Rating
Kw
F2B
3
11001
11001
2
19
IL Ignore In Test
None
FC126
0
1
0
2
1A
IL A Function
None
FC140
0
3
0
2
1B
IL A Inst Alarm
None
FC126
0
1
0
2
1C
IL A Startup Override
Seconds
F1
0
3600
0
2
1D
IL A Running Override
Seconds
F1B
0
3601
0
2
1E
IL A Healthy State
None
FC116
0
1
1
2
1F
IL B Function
None
FC140
0
3
0
2
20
IL B Inst Alarm
None
FC126
0
1
0
2
21
IL B Startup Override
Seconds
F1
0
3600
0
2
22
IL B Running Override
Seconds
F1B
0
3601
0
2
23
IL B Healthy State
None
FC116
0
1
1
2
24
Comms Ok Evaluation
None
FC131
1
64
1
2
25
Overload Pickup Level
FLA
F3
101 125
101
2
26
Unbalance K Factor
None
F1
0
19
0
2
27
Cool Time Constant
Running
Mins
F1
1
1000
15
2
28
Cool Time Constant
Stopped
Mins
F1
1
1000
30
2
29
Hot Cold Safe Stall Ratio
Percent
F1
1
100
75
2
2A
Thermal Capacity Alarm
Level
Percent
F1B
10 101
101
2
2B
Standard Overload Curve
None
F1
1
15
4
2
2C
Reserved
2D
Mechanical Jam Level
FLA
F3B
101 451
451
2
2E
Mechanical Jam Delay
Seconds
F2
1
300
1
2
2F
Acceleration Alarm Timer
Seconds
F2B
5
2501
2501
2
30
Acceleration Trip Timer
Seconds
F2B
5
2501
2501
2
31
Current Unbalance Alarm
Level
Percent
F1B
4
41
15
2
32
Current Unbalance Alarm
Delay
Seconds
F1
1
60
1
2
33
Current Unbalance Trip
Level
Percent
F1B
4
41
30
2
34
Current Unbalance Trip
Delay
Seconds
F1
1
60
1
2
ATTRIBUTE
(HEX VALUE)
DESCRIPTION
UNIT
FORMA
T CODE
MI
N
MAX
FACTOR
Y
DEFAUL
T
SIZE IN
BYTES