CHAPTER 4: FIELDBUS INTERFACE
DEVICENET PROTOCOL
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
4–61
4.
Considering the scanner’s limited memory for storage of the ADR configuration, more
than one scanner will be required if there are many MM300 relays in the DeviceNet
network.
DeviceNet Communications
The MM300 profile is an extension of the Communications Adapter Device Profile (0xC0). It
is a group 2 only server. The MAC ID and baud rate are programmable through the
EnerVista MM300 Setup software and the Graphical Control Panel. The MM300 supports
the following DeviceNet object classes.
The MM300 supports poll and explicit messaging types.
The Poll function consumes one byte of control data (described under User Object Class
B1h, Instance 01h, Attribute 01h) and produces 38 bytes of status and metering data as
described in User Object Class A0h, Instance 01h, Attribute 01h.
USINT, UINT, UDINT and DINT, stated in this document, stand for the following data types :
USINT = Unsigned integer byte
UINT = Unsigned integer word
UDINT = Unsigned integer double word
DINT = Signed integer double word
Poll data
The Polling function consumes one byte of control data and produces 38 bytes of status
and metering data as described in User Object Class A0h, Instance 01h, Attribute 01h. The
control data format is as follows:
Table 4-11: Data Value, polled output data
CLASS
OBJECT
01H
Identify
02H
Message Router
03H
DeviceNet
05H
Connection
A0H
Generic Data - Polling/Explicit
B1H
Explicit Control Writes
B0H
Analog Data - Explicit
A1H
Configuration Data - Explicit
A2H
Analog Data - Explicit
VALUE DESCRIPTION
Dec
Hex
1
0x01
Reset
2
0x02
Lockout Reset
3
0x03
Stop
4
0x04
Start A
5
0x05
Start B
66
0x42
Clear Last Trip Data Prompt
67
0x43
Reset MWh and Mvarh Meters
68
0x44
Clear Counters
69
0x45
Clear Event Records
70
0x46
Clear Waveform Data