4–8
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
PROFIBUS DP
CHAPTER 4: FIELDBUS INTERFACE
Figure 4-6: Profibus I/O data - 3 words in, 1 word out
Profibus Input Data
Category
Address (By Bytes) Length in
Bytes
Description
Format
Status-Motor
0
2
Motor Status
FC129
2
2
Extended Status
FC178
4
2
Thermal Cap Used
F1
6
4
Time to Overload Trip
F20
Start Blocks
10
2
Starts/Hour Block
F1
12
2
Time Between Starts Lockout F1B
14
2
Restart Block Lockout
F1
Learned
16
2
Average Motor Load Learned F3
18
2
Learned Acceleration Time
F2
20
4
Learned Starting Current
F10
24
2
Learned Starting Capacity
F1
Counters
26
2
Number of Motor Starts
F1
28
2
Number of UV Restarts
F1
30
4
Motor Running Hours
F9
34
2
Motor Stopped Hours
F1
Current Metering
36
4
Ia
F10
40
4
Ib
F10
44
4
Ic
F10
48
4
Iavg
F10
52
4
Igrd
F10
56
2
Motor Load
F1
58
2
Current Unbalance (I Unb)
F1
Voltage Metering
60
2
Vab
F1
62
2
Vbc
F1