2–26
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
40512
01FF
IL J Healthy State
0
1
1
---
FC116
1
1
40513
0200
Reserved
---
---
---
---
---
---
1
40514
0201
Reserved
---
---
---
---
---
---
1
40515
0202
Reserved
---
---
---
---
---
---
1
40516
0203
Reserved
---
---
---
---
---
---
1
COMMUNICATION SETUP
40517
0204
Comms OK Evaluation
1
64
1
FC131
1
1
40518
0205
Reserved
---
---
---
---
---
---
1
40519
0206
Comm Failure Trip
5
30
5
s
F1
*
30
1
40520
0207
Comm Failure Alarm
5
30
5
s
F1
*
30
1
OPEN CONTROL CIRCUIT
40521
0208
Open Ctrl Circuit Trip
0
1
1
---
FC126
0
1
40522
0209
Reserved
---
---
---
---
---
---
1
40523
020A
Reserved
---
---
---
---
---
---
1
USER MAP ADDRESSES
40524
020B
User Map Address 1
30001
43763
1
---
F1
30001
1
40525
020C
User Map Address 2
30001
43763
1
---
F1
30001
1
40526
020D
User Map Address 3
30001
43763
1
---
F1
30001
1
40527
020E
User Map Address 4
30001
43763
1
---
F1
30001
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40645
0284
User Map Address 122
30001
43763
1
---
F1
30001
1
40646
0285
User Map Address 123
30001
43763
1
---
F1
30001
1
40647
0286
User Map Address 124
30001
43763
1
---
F1
30001
1
40648
0287
User Map Address 125
30001
43763
1
---
F1
30001
1
40649
0288
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40658
0291
Reserved
---
---
---
---
---
---
1
EVENT RECORDER
40659
0292
Event Recorder Function
0
1
1
---
FC126
1
1
40660
0293
Recording of Trip Events
0
1
1
---
FC126
1
1
40661
0294
Recording of Alarm Events
0
1
1
---
FC126
1
1
40662
0295
Recording of Control Events
0
1
1
---
FC126
1
1
40663
0296
Recording of Logic Input
Events
0
1
1
---
FC126
1
1
40664
0297
Recording of Level Events
0
1
1
---
FC126
1
1
40665
0298
Recording of Dropout Events
0
1
1
---
FC126
1
1
40666
0299
Recording of Set Time/Date
Events
0
1
1
---
FC126
0
1
40667
029A
Event Record Selector
1
65535
1
---
F1
1
1
40668
029B
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40700
02BB
Reserved
1
RESET SETUP
40701
02BC
Reset Lockout Using Reset Key 0
1
0
---
FC126
0
1
THERMAL MODEL SETUP
40702
02BD
Overload Pickup Level
101
125
1
x FLA
F3
101
1
40703
02BE
Unbalance K Factor
0
19
1
---
F1
0
1
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in
Words