4–44
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL
CHAPTER 4: FIELDBUS INTERFACE
3.
Connect the power adapter to the 1770 KFD module.
4.
Connect the power out and power out common signals from the PLC power to the V-
and V+ terminals of the DeviceNet network. The terminal designations on the power
supply are shown below:
5.
Locate the DeviceNet port connector on the front of the 1747 SDN DeviceNet scanner
module and insert the 10-pin linear plug into the connector. Connect the other end of
the DeviceNet cable into this connector.
6.
Locate the DeviceNet connector on the MM300 (see top left-hand corner of the
diagram below) and connect it to the scanner using the DeviceNet Cable.
3
Drain
Shield
Non-insulated
4
CAN_H
Signal High
White
5
V+
Power Supply
Red
Terminal
Signal
Function
Color