CHAPTER 4: FIELDBUS INTERFACE
PROFIBUS DPV1
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
4–23
Table 4-7: DPV1 acyclic write data
Last Trip Data 0
0
118
2
Cause of Last Trip
FC134
0
0
120
4
Date of Last Trip 2 words
F18
0
0
124
4
Time of Last Trip 2 words
F19
0
0
128
4
Pre Trip Ia
F10
0
0
132
4
Pre Trip Ib
F10
0
0
136
4
Pre Trip Ic
F10
0
0
140
2
Pre Trip Motor Load
F1
0
0
142
2
Pre Trip Current Unbalance
F1
0
0
144
4
Pre Trip Igrd
F10
0
0
148
2
Pre Trip Vab
F1
0
0
150
2
Pre Trip Vbc
F1
0
0
152
2
Pre Trip Vca
F1
0
0
154
2
Pre Trip Van
F1
0
0
156
2
Pre Trip Vbn
F1
0
0
158
2
Pre Trip Vcn
F1
0
0
160
2
Pre Trip System Frequency
F3
0
0
162
4
Pre Trip Real Power
F13
0
0
166
4
Pre Trip Reactive Power
F13
0
0
170
2
Pre Trip Apparent Power
F2
0
0
172
2
Pre Trip Power Factor
F21
Contact Inputs 0
0
174
4
Contact Input 32-1 (Bit Field)
FC167
Contact
Outputs
0
0
178
4
Contact Output 32-1 (Bit Field)
FC167
Virtual Inputs
0
0
182
4
Virtual Input 32-1 (Bit Field)
FC167
Virtual Outputs 0
0
186
4
Virtual Output 32-1 (Bit Field)
FC167
Object
Slot
Index
Value
Description
Dec
Hex
0
0
0
1
0x01
Reset
0
0
0
2
0x02
Lockout Reset
0
0
0
4
0x04
Stop
0
0
0
8
0x08
Start A
0
0
0
16
0x10
Start B
0
0
0
66
0x42
Clear Last Trip Data Prompt
0
0
0
67
0x43
Reset MWh and Mvarh Meters
0
0
0
68
0x44
Clear Counters
0
0
0
69
0x45
Clear Event Records
0
0
0
70
0x46
Clear Waveform Data
0
0
0
71
0x47
Clear Maintenance Timer
0
0
0
72
0x48
Clear RTD Maximums
0
0
0
73
0x49
Reset Motor Information
0
0
0
74
0x4A
Auto Mode
0
0
0
75
0x4B
Manual Mode
Category
Object Slot
Index Length
(in
Bytes)
Data Item
Format