CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
FORMAT CODES
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
2–61
7
SAT
FC172
16 bits
Auto/Manual Control Stop Mode
0
Always Enabled
1
Follow Ctrl Mode
FC173
16 bits
Wire Selection
0
2W
1
3W
FC174
16 bits
Source Stop Action
0
Stop
1
Trip
FC175
16 bits
Test Auto/Manual Mode
0
ON
1
OFF
2
Unaffected
FC176
16 bits
Auxiliary VT Connection
0
Vab VT
1
Vbc VT
2
Vca VT
3
Van VT
4
Vbn VT
5
Vcn VT
6
Van Direct
7
Vbn Direct
8
Vcn Direct
FC177
16 bits
LED Color Invert
0
Green/Red
1
Red/Green
FC178
16 bits
Motor Status
Bit 0
Lockout
Bit 1
Non-Lockout Trip
Bit 2
UVR Pending
Bit 4
Running
Bit 5
Precontactor
Bit 6
Starting
Bit 8
Inhibit
Bit 9
Stopped
Bit 10
Self Test Fault
Bit 11
Alarm
Bit 12
Forward
Bit 13
Reverse
Bit 14
Low Speed
Bit 15
High Speed
FC179
32 bits
Alarm Status 1
Bit 0
Any Alarm
Bit 1
Thermal Level Alarm
Bit 2
Ground Fault Alarm
Bit 3
Acceleration Alarm
Code
Type
Definition