CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
FORMAT CODES
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
2–43
1
ON / YES
FC104
16 bits
Ground CT Type
0
None
1
Residual
2
CBCT 2000:1
FC105
16 bits
Differential CT Type
0
None
1
1 A Secondary
2
5 A Secondary
3
Direct Connect
FC106
16 bits
Voltage Transformer Connection Type
0
Wye
1
Delta
FC107
16 bits
Supply Frequency
0
60
1
50
FC109
16 bits
Flex Logic Status
0
OK
1
Unknown Token
2
Too Many Latches
3
Too Many Timers
4
Too Many + OneShots
5
Too Many - OneShots
6
Too Many Duel OneShots
7
Stack Overflow
8
Stack Underflow
9
Program Too Long
FC111
16 bits
Trip Relays
0
Trip
1
Alarm
FC112
16 bits
Communication Status
0
Error
1
OK
FC116
16 bits
Switch Type
0
Open
1
Closed
FC121
16 bits
RTD Application
0
None
1
Stator
2
Bearing
3
Ambient
4
Other
FC122
16 bits
RTD Voting Selection
0
OFF
1
RTD #1
2
RTD #2
3
RTD #3
Code
Type
Definition