CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
MODBUS MEMORY MAP
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
2–27
40704
02BF
Cool Time Constant Running
1
1000
1
min
F1
15
1
40705
02C0
Cool Time Constant Stopped
1
1000
1
min
F1
30
1
40706
02C1
Hot/Cold Safe Stall Ratio
1
100
1
%
F1
75
1
40707
02C2
Thermal Capacity Alarm Level 10
101
1
%
F1
*
101
1
40708
02C3
Standard Overload Curve
1
15
1
---
F1
4
1
40709
02C4
Reserved
---
---
---
---
---
---
1
40710
02C5
RTD Bias - Minimum T
0
251
1
°C
F1
*
251
1
40711
02C6
RTD Bias - Center T
0
251
1
°C
F1
*
251
1
40712
02C7
RTD Bias - Maximum T
0
251
1
°C
F1
*
251
1
40713
02C8
Minimize Reset Time
0
1
1
---
FC126
0
1
40714
02C9
Overload Reset Mode
0
1
1
---
FC160
1
1
40715
02CA
Reserved
---
---
---
---
---
---
1
40716
02CB
Reserved
---
---
---
---
---
---
1
40717
02CC
Reserved
---
---
---
---
---
---
1
40718
02CD
Reserved
---
---
---
---
---
---
1
MECHANICAL JAM
40719
02CE
Mechanical Jam Level
101
451
1
x FLA
F3
*
451
1
40720
02CF
Mechanical Jam Delay
1
300
1
s
F2
1
1
40721
02D0
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40724
02D3
Reserved
---
---
---
---
---
---
1
RTD TYPES
40725
02D4
Stator RTD Type
0
2
1
FC120
0
1
40726
02D5
Bearing RTD Type
0
2
1
FC120
0
1
40727
02D6
Ambient RTD Type
0
2
1
FC120
0
1
40728
02D7
Other RTD Type
0
2
1
FC120
0
1
RTD OPEN/SHORT CIRCUIT (REQUIRED=IO_G)
40729
02D8
RTD Open/Short Alarm
0
1
1
---
FC126
0
1
40730
02D9
RTD Short Circuit Alarm
0
1
1
FC126
0
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40734
02DD
Reserved
---
---
---
---
---
---
1
RTD #1 (REQUIRED=IO_G)
40735
02DE
RTD 1 Application
0
4
1
---
FC121
0
1
40736
02DF
RTD 1 Name
0
10
1
---
F22
14
10
40746
02E9
RTD 1 Alarm Temp
-50
251
1
°C
F4
*
251
1
40747
02EA
RTD 1 Trip Voting
0
6
1
---
FC122
0
1
40748
02EB
RTD 1 Trip Temp
-50
251
1
°C
F4
*
251
1
RTD #2 (REQUIRED=IO_G)
40749
02EC
RTD 2 Application
0
4
1
---
FC121
0
1
40750
02ED
RTD 2 Name
0
10
1
---
F22
15
10
40760
02F7
RTD 2 Alarm Temp
-50
251
1
°C
F4
*
251
1
40761
02F8
RTD 2 Trip Voting
0
6
1
---
FC122
0
1
40762
02F9
RTD 2 Trip Temp
-50
251
1
°C
F4
*
251
1
RTD #3 (REQUIRED=IO_G)
40763
02FA
RTD 3 Application
0
4
1
---
FC121
0
1
40764
02FB
RTD 3 Name
0
10
1
---
F22
16
10
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in
Words