CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
MODBUS MEMORY MAP
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
2–23
40240
00EF
DST End Weekday
0
7
1
---
FC170
0
1
TIME BROADCAST
40241
00F0
Time (broadcast)
0
0X173B3B63 0
F19
0
2
40243
00F2
Date (broadcast)
0
0X0C1F082E 0
F18
0
2
40244
00F3
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40261
0104
Reserved
---
---
---
---
---
---
1
VIRTUAL INPUT
40262
0105
Virtual Input 32-1 (Bit Field)
0
0xFFFFFFFF 1
FC167
0
2
40264
0107
Reserved
---
---
---
---
---
---
1
40265
0108
Reserved
---
---
---
---
---
---
1
CURRENT SENSING
40266
0109
Phase CT Type
0
3
1
---
FC105
0
1
40267
010A
CT Primary
5
1000
1
A
F1
5
1
40268
010B
Ground CT Type
0
2
1
---
FC104
2
1
40269
010C
High Speed CT Primary
5
1000
1
A
F1
5
1
40270
010D
CT Primary Turns
1
10
1
F1
1
1
40271
010E
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
40275
0112
Reserved
---
---
---
---
---
---
1
VOLTAGE SENSING
40276
0113
3 Phase Voltage Connection
0
1
1
---
FC106
0
1
40277
0114
Aux VT Connection
0
8
1
---
FC176
0
1
40278
0115
Aux VT Primary
110
690
1
V
F1
415
1
40279
0116
Aux VT Secondary
110
300
1
V
F1
110
1
40280
0117
Reserved
---
---
---
---
---
---
1
40281
0118
Reserved
---
---
---
---
---
---
1
40282
0119
Reserved
---
---
---
---
---
---
1
40283
011A
Reserved
---
---
---
---
---
---
1
MOTOR DATA SETUP
40284
011B
Supply Frequency
0
1
1
Hz
FC107
0
1
40285
011C
Motor Name
0
10
0
---
F22
3
10
40295
0126
Starter Type
0
7
1
---
FC139
0
1
40296
0127
Reserved
---
---
---
---
---
---
1
40297
0128
Reserved
---
---
---
---
---
---
1
40298
0129
Motor FLA
5
10001
1
A
F2
*
10001
1
40299
012A
High Speed FLA
5
10001
1
A
F2
*
10001
1
40300
012B
Motor Nameplate Voltage
100
690
1
V
F1
690
1
40301
012C
Change Over Current
10
51
1
x FLA
F2
*
15
1
40302
012D
Reserved
---
---
---
---
---
---
1
40303
012E
Transfer Time
0
125
1
s
F1
1
1
40304
012F
High Speed Start Block
0
1
1
---
FC126
1
1
40305
0130
Ramp Up Time
0
125
1
s
F1
1
1
40306
0131
Ramp Down Time
0
125
1
s
F1
1
1
40307
0132
Pre-contactor Time
0
60
1
s
F1
0
1
40308
0133
Motor Rating
3
11001
1
kW
F2
*
11001
1
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in
Words