CHAPTER 4: FIELDBUS INTERFACE
DEVICENET PROTOCOL
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
4–55
5.
Enter
0
in the New Device Settings: Node Address box.
6.
Click
Apply
and exit the dialog.
NOTE
NOTE:
The network must not be active when performing node commissioning on the 1747-SDN
module. Make sure the processor is in
Program
mode. (Note that this applies only to the
1747-SDN module. You may commission other devices with the processor in
Run
mode.)
Setting up the scan list for the scanner
1.
After setting node address of the scanner click on
Single Browse
from the network
menu. The 1747 SDN module should appear with the new node ID.
2.
Double-click the
1747-SDN module
icon. The following dialog will appear:
3.
Click the
Module
tab. You will receive the following prompt: