2–44
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
FORMAT CODES
CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
4
RTD #4
5
RTD #5
6
RTD #6
FC126
16 bits
Disabled / Enabled Selection
0
Disabled
1
Enabled
FC128
16 bits
Command Status
0
Manual
1
Auto
2
Manual Inhibit
3
Auto/ Manual
4
Hardwired Auto
5
None
FC129
16 bits
Quick Status
Bit 0
Alarm
Bit 1
Trip
Bit 2
Self Test Fault
Bit 3
Auto
Bit 4
Contactor A
Bit 5
Contactor B
Bit 6
Contact Output 3
Bit 7
Drive Available
FC130
16 bits
LED Flash
Bit 0
Running
Bit 1
Stopped
Bit 2
Tripped
Bit 3
Alarm
Bit 4
Comms OK
Bit 5
Auto
Bit 6
Manual
Bit 7
USER1
Bit 8
USER2
Bit 9
USER3
Bit 10
50%
Bit 11
80%
Bit 12
100%
FC131
16 bits
Comm Fail Mode
1
Serial
2
Serial & Ethernet
4
Serial & FieldBus
8
Ethernet
16
FieldBus
32
Ethernet & Fieldbus
64
All
FC133
16 bits
CAUSE OF WAVEFORM/DATA LOG TRIGGER
0
None
1
Command
Code
Type
Definition