GE Grid Solutions
iBox/iBox Kit
Installation and Maintenance Guide
GE Information
994-0047-5.10-4
161
DCA
DPA
Source Data
Type
MODBUS DCA
Register
Address
Point Description
COM1
COM2
DNP DPA
Point
MODBUS DPA
Point Address
DNP TCP/IP
DPA Point
M
O
DBUS
DCA
(IB
O
X-
ACA a
nd
IBO
X-
ACL
)
cont
in
ued
AI
406
VAR MIN
80
81
80
407
VA MIN
81
82
81
408
PF MIN
82
83
82
409
FREQ MIN
83
84
83
1282
RESET VOLT/AMP/POWER
84
85
84
1284
RESET MAX/MIN/WH
85
86
85
AO
1282
RESET VOLT/AMP/POWER
0
89
0
1284
RESET MAX/MIN/WH
1
90
1
CT
434
WATT HOUR BCD COUNTER 8
N/A
N/A
N/A
435
WATT HOUR BCD COUNTER 7
N/A
N/A
N/A
436
WATT HOUR BCD COUNTER 6
N/A
N/A
N/A
437
WATT HOUR BCD COUNTER 5
N/A
N/A
N/A
438
WATT HOUR BCD COUNTER 4
N/A
N/A
N/A
439
WATT HOUR BCD COUNTER 3
N/A
N/A
N/A
440
WATT HOUR BCD COUNTER 2
N/A
N/A
N/A
441
WATT HOUR BCD COUNTER 1
N/A
N/A
N/A
Lo
gi
cL
in
x
CT
N/A
KWH counter 32bit
0
N/A
0
N/A
KWH counter 16bit MSB
N/A
87
N/A
N/A
KWH counter 16bit LSB
N/A
88
N/A
Notes:
•
ADAM-4017 AI CH: 00 to 07 are converted by the Calculator DTA into two's compliment numbers
which are stored in the system point database (Scaled Analog Input #1 to 8).
•
WATT HOUR BCD COUNTER 1 to 8 of the AC meter are ASCII BCD numbers. These numbers are
converted into KW HOUR (KWH counter 32bit) by LogicLinx to be passed to the DNP master. Then
"KWH counter 32bit" is converted into two 16-bit counters (KWH counter 16bit MSB and KWH
counter 16bit LSB) to be passed to the MODBUS master.