iBox/iBox Kit
Installation and Maintenance Guide
GE Grid Solutions
54
994-0047-5.10-4
GE Information
Digital Outputs
Operating
Modes
iBox control outputs have two modes of operation:
•
Trip/Close (T/C) pairs
•
Digital Output (DO) isolation Form A contacts.
Note:
Using SGConfig, you must configure the digital outputs for four Trip/Close
outputs or two Trip/Close and two digital outputs, depending on the part number.
Wiring Four
Trip/Close
Outputs
(Part No.
505-0100,
505-0101,
505-0102)
You can wire four trip/close outputs, as follows:
Wiring Two
Trip/Close
and Two
Digital
Outputs
(Part No.
505-0103,
505-0104,
505-0105)
You can wire two trip/close and two digital outputs, as follows:
Important
iBox digital outputs are not internally fuse-protected.
Remote/Local
Operation
If:
Then operation is:
JP2 is installed Remote (controls are enabled)
JP2 is removed
Local (controls are disabled)
TB15
TB14
TB13
TB12
TB11
Trip 4
Close 4
Trip 3
Close 3
Trip 2
Close 2
Trip 1
Close 1
1
2
1
2
1
2
1
2
1
2
Master T/C
(+/- V)
GND
TB15
TB14
TB13
TB12
TB11
Trip 2
Close 2
Trip 1
Close 1
1
2
1
2
1
2
1
2
1
2
Master T/C
(+/- V)
GND
Digital Out 2
(Form A)
Digital Out 1
(Form A)
Summary of Contents for iBox