Digital Output Verification Test
, continued
Procedure: Testing Digital Outputs
, continued
Step
Action
7
Press the
SPACE BAR
to select
Pulse,
and press
ENTER
.
8
In the
Off time
field, type
500
and press
ENTER
.
9
In the
On time
field, type
500
and
press
ENTER
.
10
In the
Repeat Command
field, type
10
and press
ENTER
twice.
Result:
Listen carefully for an audible click of the point relay. A test is
considered successful if the relays click when forced.
11
For testing
Trip/Close
type operation, repeat steps 1- 6.
12
Press the
SPACE BAR
to select
Trip/Close,
and press
ENTER
.
13
In the
Off time
field, type
300
and press
ENTER
.
14
In the
On time
field, type
300
and
press
ENTER
.
15
In the
Repeat Command
field, type the value
0
and press
ENTER
twice.
Result:
Listen carefully for an audible click of the point relay. A test is
considered successful if the relays click when forced.
Note:
For Trip/Close operation in
Repeat Command
field, if field
input value is other than zero it results in a WIN write request
failed error message with status 0x0011 (operation not supported
for this point).Refer to
Notes
Note:
The password shown above is factory default. If you cannot log in, contact
your system administrator to obtain the new password.
Note:
The number of times that a control will operate is actually N+1, where N is
the number of repeats entered in the
Repeat command
field. For a single
operation, with no repeats, type
0
. For two operations, type
1.
Test Failure
If relays do not operate:
1.
Ensure that the
CONTROLS
enable jumper is in the
REMOTE
position. No
error message appears in WESMAINT if the test fails
2.
Reboot the iBox, and repeat the procedure
3.
Call GE Digital Energy for assistance
Repeat Test
To repeat the test sequence, press
CTRL
+
U
,
and then press
ENTER
.
Values entered for the previous test are retained until you exit the menu.
Test Next
Point
To test another point, use the
UP
or
DOWN
arrows to cycle through points, then press
CTRL
+
U
to repeat the test.