750/760 Feeder Management Relay
GE Power Management
12.7 VOLTAGE
12 S5 PROTECTION
12
12.7.5 OVERVOLTAGE
To protect voltage sensitive loads and circuits against sustained overvoltage conditions, the overvoltage 1 and
2 protection features can be used to either cause a trip or generate an alarm when the voltage exceeds a spec-
ified voltage setting for a specified time delay.
The following setpoints are repeated for both Overvoltage 1 and Overvoltage 2.
■
OVERVOLTAGE 1
■
[ENTER] for more
The Overvoltage 1 setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ VOLTAGE \ OVERVOLTAGE 1
OVERVOLTAGE 1
FUNCTION: Disabled
Range: Disabled, Trip, Alarm, Latched Alarm, Control
Select the required function.
OVERVOLTAGE 1
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
OVERVOLTAGE 1
PICKUP: 1.25 x VT
Range: 0.00 to 1.25 in steps of 0.01 x VT
Selects the pickup as a fraction of the nominal bus VT Secondary Voltage. For
example, if the nominal VT secondary voltage is 120 V, and an alarm is
required whenever the voltage exceeds 130 V, enter 130 / 120 =
1.08
for the
pickup.
OVERVOLTAGE 1
DELAY:
2.0 s
Range: 0.0 to 6000.0 in steps of 0.1 s
Selects the delay required.
PHASES REQUIRED FOR
OPERATION: All Three
Range: Any One, Any Two, All Three
Select the type of operation required.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...