14-
32
750/760 Feeder Management Relay
GE Power Management
14.8 AUTORECLOSE (760 ONLY)
14 S7 CONTROL
14
AR EXTERNAL CLOSE
LOGIC: Disabled
Range: Enabled, Disabled
For applications where the breaker may be closed directly, without using the
760 to provide the closing signal to the breaker, enabling this setpoint will use
breaker state to determine if a manual close has occurred.
The 760 uses the detection of a manual close to disable the autoreclose
scheme to prevent reclosing onto a fault. Also, if the Autoreclose scheme is in
the lockout state, a successful manual close would result in the autoreclose
scheme being automatically reset after the
AR BLOCK TIME UPON MANUAL CLOSE
time has expired.
When
Enabled
, this setpoint uses the detection of the breaker going from the
open state to the closed state to determine if a manual close has occurred.
The breaker state is determined by the 52a/b contact feedback to the 760.
When
Disabled
, only close commands sent via the 760 will be considered as a
manual close for the autoreclose scheme logic.
INCOMPLETE SEQUENCE
TIME:
30 s
Range: 1 to 1000 in steps of 1 s
This timer is used to set the maximum time interval allowed for a single reclose
shot. It is started whenever a reclosure is initiated and is active when the
scheme is in the ‘Reclosure In Progress’ state. If all conditions allowing a
breaker closure are not satisfied when this timer expires, the reclosure initia-
tion is abandoned. Any combinations of the following conditions block the
breaker from closing.
Breaker status logic inputs (52a or 52b contact) fail to report the breaker has
opened.
The ‘Block 2 Close Relay’ logic input function is asserted.
The synchrocheck feature is blocking breaker closes.
NOTE: This timer must be set to a delay less than the autoreclose reset
timer.
RECLOSURE ENABLED
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the relays required to operate while the front panel RECLOSURE
ENABLED indicator is on.
RECLOSER IN PROGRESS
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the relays required to operate while the front panel RECLOSURE IN
PROGRESS indicator is on. This indicator is on when the autoreclose scheme
has been initiated, but has not yet sent a close command. This output could be
used to block the operation of a transformer tap changer during a reclosure
sequence.
RECLOSURE LOCKOUT
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the relays required to operate while the front panel RECLOSURE
LOCKOUT indicator is on. This indicator is on when the autoreclose scheme
has progressed to a lockout condition, such that no further breaker closures
will be initiated until the 760 has been reset.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...