750/760 Feeder Management Relay
GE Power Management
5.3 KEYPAD OPERATION
5 FRONT PANEL OPERATION
5
5.3 KEYPAD OPERATION
5.3.1 DESCRIPTION
The 750/760 display messages are organized into pages under the headings Setpoints and Actual Values. The
key navigates through the page headers of programmable parameters (Setpoints). The
key nav-
igates through the page headers of measured parameters (Actual Values). Each page is broken down further
into logical subpages of messages. The
and
keys are used to navigate through the sub-
pages. A summary of the setpoints and actual values pages can be found in the Chapters 7: SETPOINTS and
6: ACTUAL VALUES, respectively.
The
key is dual purpose. It is used to enter the subpages and to store altered setpoint values into mem-
ory to complete the change. The
key is also dual purpose. It is used to exit from subpages and also to
abort a setpoint change.
The
and
keys are used to scroll through the possible choices of an enumerated setpoint.
They also decrement and increment numerical setpoints. Numerical setpoints may also be entered through the
numeric keypad.
The
key may be pressed at any time to display a list of context sensitive help messages. Continue to
press the
key to display all the help messages and return to the original display.
The
key will reset any latched conditions that are not presently active. This includes resetting latched
output relays, latched TRIP indicators, breaker operation failure, and trip / close coil failures. The 760 autore-
close scheme is also reset with the shot counter being returned to zero and the lockout condition being
cleared.
The
key scrolls through any active conditions in the relay. Diagnostic messages are displayed indicating
the state of protection and monitoring elements that are picked up, operating, or latched. When the MESSAGE
indicator light is on there are messages to be viewed with the
key.
Pressing the
key will attempt to open the breaker connected to the 1 TRIP relay by closing the contact.
Likewise, the
key will attempt to close the breaker connected to the 2 CLOSE relay by closing the con-
tact. The
and
keys only operate when the relay is in local mode; local mode can be enabled with
a user programmed logic input.
A C T U A L
E N T E R
E S C A P E
V A LU E
V A LU E
H E L P
H E L P
R E S E T
N E X T
N E X T
O P E N
C L O S E
O P E N
C L O S E
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...