16-
50
750/760 Feeder Management Relay
GE Power Management
16.4 MODBUS MEMORY MAP
16 COMMUNICATIONS
16
S6
TOTAL ARCING CURRENT
READ/WRITE
1908
Total Arcing Current Function
---
---
F38
Disabled
1909
Total Arcing Current Relays
---
---
F57
None
190A
Total Arcing Current Start Delay
0 to 100
ms
F1
32 ms
190B
Total Arcing Current Limit
1 to 50000
kA
2
-cyc
F1
1000 kA
2
cyc
S6
VT FAILURE
READ/WRITE
1918
VT Failure Function
---
---
F38
Disabled
1919
VT Failure Relays
---
---
F57
None
191A
VT Failure Delay
0 to 60,000
s
F1
10 s
S8
SIMULATION SETUP
READ/WRITE
1920
Simulation Status
---
---
F48
Disabled
1921
Circuit Breaker Simulation
---
---
F30
Enabled
1922
Allow Operation of Relays
---
---
F57
None
S8
SIMULATION PRE-FAULT VALUES
READ/WRITE
1930
Prefault Phase A/B/C Current Level
0.00 to 20.00
x CT
F3
0.50 x CT
1931
Prefault Power Factor Angle
0 to 359
° Lag
F1
0° Lag
S8
SIMULATION FAULT VALUES
READ/WRITE
1940
Fault Phase A-N Voltage Level
0.00 to 2.00
x VT
F3
1.00 x VT
1941
Fault Phase A-N Voltage Position
0 to 359
° Lag
F1
0° Lag
1942
Fault Phase B-N Voltage Level
0.00 to 2.00
x T
F3
1.00 x VT
1943
Fault Phase B-N Voltage Position
0 to 359
° Lag
F1
120° Lag
1944
Fault Phase C-N Voltage Level
0.00 to 2.00
x T
F3
1.00 x VT
1945
Fault Phase C-N Voltage Position
0 to 359
° Lag
F1
240° Lag
1946
Fault Phase A Current Level
0.00 to 20.00
x CT
F3
1.00 x CT
1947
Fault Phase A Current Position
0 to 359
° Lag
F1
60° Lag
1948
Fault Phase B Current Level
0.00 to 20.00
x CT
F3
1.00 x CT
1949
Fault Phase B Current Position
0 to 359
° Lag
F1
180° Lag
194A
Fault Phase C Current Level
0.00 to 20.00
x CT
F3
1.00 x CT
194B
Fault Phase C Current Position
0 to 359
° Lag
F1
300° Lag
194C
Fault System Frequency
20.00 to 65.00
Hz
F3
60.00 Hz
194D
Fault Analog Input Current
0.00 to 20.00
mA
F3
0.00 mA
194E
3
Reserved for Fault Polarizing Current Level
0.00 to 20.00
x CT
F70
1.00 x CT
194F
3
Reserved for Fault Polarizing Current Position
0 to 359
° Lag
F1
0°
1950
Fault Ground Current Level
0.00 to 20.00
x CT
F3
0.00 x CT
1951
Fault Ground Current Position
0 to 359
° Lag
F1
0°
1952
3
Fault Sensitive Ground Current Level
0.005 to 1.000
x CT
F70
0.100 x CT
Table 16–15: MODBUS MEMORY MAP (Sheet 33 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...