GE Power Management
750/760 Feeder Management Relay
16-
7
16 COMMUNICATIONS
16.3 MODBUS PROTOCOL
16
16.3.6 FUNCTION CODE 03H/04H: READ ACTUAL VALUES/SETPOINTS
This function code allows the master to read one or more consecutive data registers (actual values or set-
points) from an 750/760. Data registers are always 16 bit (two byte) values transmitted high order byte first.
The maximum number of registers that can be read in a single packet is 120. See the section MEMORY MAP
for exact details on the data registers.
Since some PLC implementations of Modbus only support one of function codes 03h and 04h, the 750/760
interpretation allows either function code to be used for reading one or more consecutive data registers. The
data starting address will determine the type of data being read. Function codes 03h and 04h are therefore
identical.
The following table shows the format of the master and slave packets. The example shows a master device
requesting 3 register values starting at address 200h from slave device 11; the slave device responds with the
values 555, 0, and 100 from registers 200h, 201h, and 202h respectively.
Table 16–3: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 03H/04H
MASTER TRANSMISSION
SLAVE RESPONSE
PACKET FORMAT
EXAMPLE (HEX)
PACKET FORMAT
EXAMPLE (HEX)
SLAVE ADDRESS
11
SLAVE ADDRESS
11
FUNCTION CODE
03
FUNCTION CODE
03
DATA STARTING ADDRESS - hi
02
BYTE COUNT
06
DATA STARTING ADDRESS - lo
00
DATA #1 - hi
02
NUMBER OF REGISTERS - hi
00
DATA #1 - lo
2B
NUMBER OF REGISTERS - lo
03
DATA #2 - hi
00
CRC - lo
06
DATA #2 - lo
00
CRC - hi
E3
DATA #3 - hi
00
DATA #3 - lo
64
CRC - lo
C8
CRC - hi
BA
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...