10 S3 LOGIC INPUTS
10.10 MISCELLANEOUS FUNCTIONS
10
10.10 MISCELLANEOUS FUNCTIONS
10.10.1 DESCRIPTION
The following logic input functions do not fall into any specific category and thus are listed together under mis-
cellaneous functions.
10.10.2 SETTINGS
■
MISC FUNCTIONS
■
[ENTER] for more
The Miscellaneous Functions setpoints path is:
\ SETPOINTS \ S3 LOGIC INPUTS \ MISCELLANEOUS
TRIGGER TRACE
MEMORY: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Triggers a Trace Memory waveform capture.
TRIGGER DATA LOGGER:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Triggers a Data Logger sample capture.
SIMULATE FAULT:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
This input function is operational only when the relay is in simulation testing
mode, the breaker is closed (real or simulated breaker) and presently in the
prefault state. When the assigned input is asserted, the relay is forced into the
fault state where the programmed ‘fault’ values are used.
START DEMAND
INTERVAL: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
This input begins the new demand interval for all Block Interval demand calcu-
lations.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...