8-
2
750/760 Feeder Management Relay
GE Power Management
8.2 COMMUNICATIONS
8 S1 RELAY SETUP
8
8.2 COMMUNICATIONS
8.2.1 DESCRIPTION
Up to 32 devices can be daisy-chained with one of them a computer or programmable controller. Either COM1,
the two wire RS485 or the four wire RS422 serial communication port, or COM2, the two wire RS485 port may
be used. One relay can be connected directly to a personal computer via the front panel RS232 port with a
standard, straight-through RS232 cable.
8.2.2 SETTINGS
■
PORT SETUP
■
[ENTER] for more
The Communications setpoints path is:
\ SETPOINTS \ S1 RELAY SETUP \ COMMUNICATIONS \ PORT SETUP
SLAVE ADDRESS:
1
Range: 1 to 254 in steps of 1
Selects the serial communications slave address of the relay. Both COM1 and
COM2 use this same address. The front panel RS232 port will accept any
address for normal communications, but must be set to 1 when upgrading the
relay firmware. Each relay on the same RS485/422 communications link must
have a unique address.
COM1 RS485/422
BAUD RATE: 9600
Range: 300, 1200, 2400, 4800, 9600, 19200
Select the baud rate for COM1, the RS485/RS422 communication port. All
relays on the communication link, and the computer connecting them, must
run at the same baud rate. The fastest response will be obtained at
19200
Baud. Slower baud rates should be used if noise becomes a problem. The
data frame is fixed at 1 start, 8 data, and 1 stop bit.
COM1 RS485/422
PARITY: None
Range: None, Odd, Even
Selects the parity for COM1.
COM1 RS485/422
HARDWARE: RS485
Range: RS485, RS422
Selects the COM1 hardware configuration to be either two wire RS485 or four
wire RS422 communications.
COM2 RS485/422
BAUD RATE: 9600
Range: 300, 1200, 2400, 4800, 9600, 19200
Selects the baud rate for COM2, the rear terminal RS485 communication port.
COM2 RS485/422
PARITY: None
Range: None, Odd, Even
Selects the parity for COM2.
FRONT RS232
BAUD RATE: 9600
Range: 300, 1200, 2400, 4800, 9600, 19200
Selects the baud rate for front panel RS232 serial communications port. When
upgrading the relay firmware, this rate should be set to
9600
Baud.
FRONT RS232
PARITY: None
Range: None, Odd, Even
Selects the parity for the front RS232 port.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...