GE Power Management
750/760 Feeder Management Relay
16-
53
16 COMMUNICATIONS
16.4 MODBUS MEMORY MAP
16
1B14
2
Live Bus Minimum Voltage
0.00 to 1.25
x VT
F3
0.80 x VT
1B15
2
Live Line Minimum Voltage
0.00 to 1.25
x VT
F3
0.80 x VT
1B16
2
Maximum Voltage Difference
0.01 to 100.00
kV
F3
2.00 kV
1B17
Maximum Angle Difference
0 to 100
°
F1
24°
1B18
Maximum Frequency Difference
0 to 5.00
Hz
F3
2.00 Hz
1B19
Synchrocheck Relays
---
---
F57
None
S7
MANUAL CLOSE FEATURE BLOCKING
READ/WRITE
1B20
Manual Close Feature Blocking Function
---
---
F38
Disabled
1B21
Manual Close Relays
---
---
F57
None
1B22
2
Manual Close Block Time
1 to 1000
s
F1
5 s
1B23
1
Select Setpoint Group
---
---
F80
Active Group
1B24
2
Overcurrent Blocking Flags
---
---
F59
None blocked
1B25
2
Phase Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1B26
2
Neutral Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1B27
2
Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
1B28
2
N egative S equence Tim e O vercurrent R aised P ickup
0 to 100
%
F1
0%
1B29
3
Sensitive Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
S7
COLD LOAD FEATURE BLOCKING
READ/WRITE
1B40
Cold Load Pickup Feature Blocking Function
---
---
F38
Disabled
1B41
Cold Load Pickup Relays
---
---
F57
None
1B42
Outage Time Before Cold Load
1 to 1000
min.
F1
100 min.
1B43
2
Cold Load Pickup Block Time
1 to 1000
s
F1
5 s
1B44
1
Select Setpoint Group
---
---
F80
Active Group
1B45
2
Overcurrent Blocking Flags
---
---
F59
None blocked
1B46
2
Phase Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1B47
2
Neutral Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1B48
2
Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
1B49
2
N egative S equence Tim e O vercurrent R aised P ickup
0 to 100
%
F1
0%
1B4A
3
Sensitive Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
S7
UNDERVOLTAGE RESTORATION
READ/WRITE
1B60
Undervoltage Restoration Function
---
---
F38
Disabled
1B61
Undervoltage Restoration Relays
---
---
F57
None
1B62
U nde rvoltag e R e sto ration P h ases R e quired for O pe ration
---
---
F41
All Three
1B63
2
Undervoltage Restoration Minimum Voltage
0.00 to 1.25
x VT
F3
0.90 x V
Table 16–15: MODBUS MEMORY MAP (Sheet 36 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...