![GE 750 Instruction Manual Download Page 111](http://html.mh-extra.com/html/ge/750/750_instruction-manual_131794111.webp)
GE Power Management
750/760 Feeder Management Relay
8-
1
8 S1 RELAY SETUP
8.1 PASSCODE
8
8 S1 RELAY SETUP 8.1 PASSCODE
8.1.1 DESCRIPTION
To program setpoints, besides the setpoint access jumper that must be installed on the rear terminals, a pass-
code must also be entered if the passcode security feature is enabled. When the relay is shipped from the fac-
tory the passcode is defaulted to ‘0’. When the passcode is ‘0’, the passcode security feature is always
disabled and only the setpoint access jumper is required for changing setpoints from the front panel.
8.1.2 SETTINGS
■
PASSCODE
■
[ENTER] for more
The PASSCODE setpoints path is:
\ SETPOINTS \ S1 RELAY SETUP \ PASSCODE
SETPOINT ACCESS:
Allowed
Range: Allowed, Restricted (Cannot Be Edited)
This indicates whether passcode protection is currently enabled.
RESTRICT ACCESS TO
SETPOINTS? No
Range: Yes, No
This message is only displayed when setpoint access is allowed and the cur-
rent passcode is not ‘0’. Select
Yes
and follow directions to restrict setpoint
access.
ALLOW ACCESS TO
SETPOINTS? No
Range: Yes, No
This message is only displayed when setpoint access is restricted. In this
state, new setpoints cannot be entered. In order to regain setpoint access,
select
Yes
and follow directions to enter the passcode that was previously pro-
grammed. If the passcode is correctly entered, entering new setpoints will be
allowed. If no keys are pressed for longer than 30 minutes, setpoint access will
automatically become restricted. Removing the setpoint access jumper will
immediately restrict setpoint access. If passcode protection is active but the
passcode is not known, the factory should be contacted with the encrypted
passcode value.
CHANGE PASSCODE?
No
Range: Yes, No
To change the current passcode, select
Yes
and follow directions. Note that
changing the passcode to ‘0’, as it is when shipped from the factory, will dis-
able the passcode security feature.
ENCRYPTED PASSCODE:
AIKFBAIK
Range: (Cannot Be Edited)
If the programmed passcode is not known, consult the factory service depart-
ment with the 8 character word displayed.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...