GE Power Management
750/760 Feeder Management Relay
13-
35
13 S6 MONITORING
13.8 EQUIPMENT
13
13.8.5 COIL MONITOR
COIL MONITOR 1
and
2
are programmed in this subgroup. They are two identical elements that may be used to
monitor trip or close coils. The operation of this feature is described in Section 3.2.11: TRIP / CLOSE COIL
SUPERVISION on page 3–13.
■
COIL MONITOR 1
■
[ENTER] for more
The Coil Monitor 1 setpoints path is:
\ SETPOINTS \ S6 MONITORING \ EQUIPMENT \ COIL MONITOR 1
COIL MONITOR 1 NAME:
Trip Coil Monitor
Range: Any Combination of 18 Alphanumeric Characters
An 18 character field that will be displayed as part of the diagnostic messages
and event recorder when events associated with this element occur.
COIL MONITOR 1
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
Select the required function.
COIL MONITOR 1
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
BREAKER STATE
BYPASS: Disabled
Range: Enabled, Disabled
Detection of a failed circuit regardless of the breaker state (i.e. detection of a
failed trip circuit when the breaker is open) requires
BREAKER STATE BYPASS
to
be
Enabled
. Generally, this selection will require a wiring modification of the
breaker, as detailed in Chapter 3: INSTALLATION.
COIL MONITOR 1
DELAY: 5 s
Range: 5 to 100 in steps of 1 s
Select the delay required.
COIL MONITOR 1
TYPE: Trip
Range: Trip, Close
Select the type of coil being monitored.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...