GE Power Management
750/760 Feeder Management Relay
16-
35
16 COMMUNICATIONS
16.4 MODBUS MEMORY MAP
16
135A
Relay 6 AUXILIARY Pulse Dwell Time
0.1 to 6000.0
s
F2
0.1 s
S4
RELAY 7 AUXILIARY
READ/WRITE
1360
Relay 7 AUXILIARY Name (8 words)
---
---
F33
"AUXILIARY"
1368
Relay 7 AUXILIARY Non-operated State
---
---
F34
De-energized
1369
Relay 7 AUXILIARY Output Type
---
---
F35
Self-resetting
136A
Relay 7 AUXILIARY Pulse Dwell Time
0.1 to 6000.0
s
F2
0.1 s
S3
8
USER INPUT I
READ/WRITE
1370
8
User Input I Name (9 registers)
---
---
F33
User Input I
1379
8
User Input I Source
---
---
F65
Disabled
137A
8
User Input I Function
---
---
F37
Disabled
137B
8
User Input I Relays
---
---
F57
None
137C
8
User Input I Delay
0.00 to 600.00
s
F3
0.00 s
S3
8
USER INPUT J
READ/WRITE
1380
8
User Input J Name (9 registers)
---
---
F33
User Input J
1389
8
User Input J Source
---
---
F65
Disabled
138A
8
User Input J Function
---
---
F37
Disabled
138B
8
User Input J Relays
---
---
F57
None
138C
8
User Input J Delay
0.00 to 600.00
s
F3
0.00 s
S3
8
USER INPUT K
READ/WRITE
1390
8
User Input K Name (9 registers)
---
---
F33
User Input K
1399
8
User Input K Source
---
---
F65
Disabled
139A
8
User Input K Function
---
---
F37
Disabled
139B
8
User Input K Relays
---
---
F57
None
139C
8
User Input K Delay
0.00 to 600.00
s
F3
0.00 s
S3
8
USER INPUT L
READ/WRITE
13A0
8
User Input L Name (9 registers)
---
---
F33
User Input L
13A9
8
User Input L Source
---
---
F65
Disabled
13AA
8
User Input L Function
---
---
F37
Disabled
13AB
8
User Input L Relays
---
---
F57
None
13AC
8
User Input L Delay
0.00 to 600.00
s
F3
0.00 s
S3
8
USER INPUT M
READ/WRITE
13B0
8
User Input M Name (9 registers)
---
---
F33
User Input M
13B9
8
User Input M Source
---
---
F65
Disabled
Table 16–15: MODBUS MEMORY MAP (Sheet 18 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...