16 COMMUNICATIONS
16.4 MODBUS MEMORY MAP
16
76
1
Zero Sequence Voltage Angle
77
3
Sensitive Ground Current
78
3
Sensitive Ground Current Angle
79
4
Neutral Voltage
80
4
Neutral Voltage Angle
F78
2
ANALOG OUTPUT MINIMUM / MAXIMUM
The Range, Step Value, and Units for the Analog Output Minimum and Maximum depends
upon the parameter type programmed for the output. The following table shows the format for
a given parameter type:
F79
SETPOINT GROUP
0
Group 1
1
Group 2
2
Group 3
3
Group 4
F80
EDIT SETPOINT GROUP
0
Group 1
1
Group 2
2
Group 3
3
Group 4
4
Active Group
F81
TRACE MEMORY / DATA LOGGER BUFFER ORGANIZATION
0
2 x 2048
1
4 x 1024
2
8 x 512
3
16 x 256
Table 16–16: MODBUS MEMORY MAP DATA FORMATS (Sheet 22 of 24)
TYPE
VALUE / BIT
MASK
DESCRIPTION
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–83.
PARAMETER
RANGE
STEP
UNITS
All currents
0 to 65535
1
Amps
All voltages
0.00 to 655.35
0.01
kV
% Load to Trip
0 to 2000
1
%
Frequency
20.00 to 65.00
0.01
Hz
All Power / Energy
see F86
Power Factor
-0.99 to +1.00
0.01
---
Analog Input
0 to 65535
1
units
Fault Location
-1000.0 to +1000.0
0.1
km / miles
Frequency Delay
-10.00 to +10.00
0.01
Hz/s
All Angles
0 to 359
1
° Lag
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...