17.7 PROTECTION SCHEMES
17 COMMISSIONING
17
Indications and Operations caused by a Trip Function, with Logic Input Resetting:
1.
Ensure that the reset logic input control function has been assigned to a logic input.
2.
Perform steps 1 through 3 above.
3.
Assert a logic input to provide a reset. Check that the TRIP and MESSAGE indicators are now off, and the
Last Trip message is no longer displayed. Turn current off.
Indications and Operations caused by an Alarm Function:
1.
Inject current to cause a pickup and wait until the element times to Alarm. Check that the ALARM and
MESSAGE indicators are flashing, the Active Alarm message is displayed, and any output relays pro-
grammed to operate (as well as their associated LED indicators) operate.
2.
Slowly reduce the current until the PICKUP indicator goes out. Check that the ALARM and MESSAGE
indicators go off, and that any output relays programmed to operate (as well as their associated LED indi-
cators) reset, and the Active Alarm message is no longer displayed. Turn current off.
Indications and Operations caused by a Control Function:
1.
Inject current to cause a pickup and wait until the element times-out. Check that any output relays pro-
grammed to operate (as well as their associated LED indicators) operate.
2.
Slowly reduce the current until the PICKUP indicator goes out. Check that any output relays programmed
to operate (as well as their associated LED indicators) reset. Turn current off.
Indications and Operations caused by a Latched Alarm Function, with front panel RESET Key Reset-
ting:
1.
Inject current to cause a pickup and wait until the element times to Alarm.
2.
Check that the ALARM and MESSAGE indicators are flashing, the Active Alarm message is displayed, and
any output relays programmed to operate (as well as their associated LED indicators) operate.
3.
Slowly reduce the current until the PICKUP indicator goes out. Check that the ALARM and MESSAGE
indicators are flashing, and that any output relays programmed to operate (as well as their associated LED
indicators) reset.
4.
Press the front panel RESET key. Check that the ALARM and MESSAGE indicators go off, and the Active
Alarm message is no longer displayed. Turn current off.
Blocking From Logic Inputs:
1.
Inject current to cause a pickup.
2.
Assert a logic input to provide a "Block Phase Time 1". The PICKUP indicator should immediately go out.
3.
Repeat steps 1 and 2 for logic inputs "Block Phase O/C", "Block All O/C" and “Block 1 TRIP Relay” as
required.
Timing:
1.
Connect the Stop Trigger.
2.
Preset the injection current level to 2.0 x pickup. Turn the current off, and reset the timer.
3.
Inject the preset current into phase A and note the measured delay time. Check this time against the time
established by the settings. Reset the timer.
4.
Preset the injection current level to 4.0 x pickup. Turn the current off, and reset the timer.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...