750/760 Feeder Management Relay
GE Power Management
3.2 TYPICAL WIRING
3 INSTALLATION
3
3.2.2 REAR TERMINAL ASSIGNMENTS
ANALOG INPUT / OUTPUTS
OUTPUT RELAYS
A1
ANALOG INPUT +
E1
SOLID STATE TRIP OUT +
A2
ANALOG INPUT -
E2
1 TRIP RELAY NO
A3
SHIELD (GROUND)
E3
2 CLOSE RELAY NO
A4
ANALOG OUTPUT -
E4
3 AUXILIARY RELAY NO
A5
ANALOG OUTPUT 1 +
E5
3 AUXILIARY RELAY NC
A6
ANALOG OUTPUT 2 +
E6
4 AUXILIARY RELAY NC
A7
ANALOG OUTPUT 3 +
E7
5 AUXILIARY RELAY NC
A8
ANALOG OUTPUT 4 +
E8
5 AUXILIARY RELAY NO
A9
ANALOG OUTPUT 5 +
E9
6 AUXILIARY RELAY NC
A10
ANALOG OUTPUT 6 +
E10
7 AUXILIARY RELAY NC
A11
ANALOG OUTPUT 7 +
E11
7 AUXILIARY RELAY NO
A12
ANALOG OUTPUT 8 +
E12
8 SELF-TEST WARNING RELAY NC
COMMUNICATION
OUTPUT RELAYS
B1
COM1 RS485 +
F1
SOLID STATE TRIP OUT -
B2
COM1 RS485 -
F2
1 TRIP RELAY COM
B3
COM1 RS485 COM
F3
2 CLOSE RELAY COM
B4
COM1 RS422 TX +
F4
3 AUXILIARY RELAY COM
B5
COM1 RS422 TX -
F5
4 AUXILIARY RELAY NO
B6
COM2 RS485 +
F6
4 AUXILIARY RELAY COM
B7
COM2 RS485 -
F7
5 AUXILIARY RELAY COM
B8
COM2 RS485 COM
F8
6 AUXILIARY RELAY NO
B9
SHIELD (GROUND)
F9
6 AUXILIARY RELAY COM
B10
IRIG-B +
F10
7 AUXILIARY RELAY COM
B11
IRIG-B -
F11
8 SELF-TEST WARNING RELAY NO
B12
RESERVED
F12
8 SELF-TEST WARNG RELAY COM
LOGIC INPUTS
CT and VT INPUTS / GROUND
C1
LOGIC INPUT 1
G1
COIL MONITOR 1 +
C2
LOGIC INPUT 2
G2
COIL MONITOR 2 +
C3
LOGIC INPUT 3
G3
SENSITIVE GROUND CT
■
C4
LOGIC INPUT 4
G4
SYNCHRO VT
■
(LINE)
C5
LOGIC INPUT 5
G5
PHASE A VT
■
(BUS)
C6
LOGIC INPUT 6
G6
PHASE C VT
■
(BUS)
C7
LOGIC INPUT 7
G7
PHASE A CT
■
C8
RESERVED
G8
PHASE B CT
■
C9
RESERVED
G9
PHASE C CT
■
C10
SETPOINT ACCESS –
G10
GROUND CT
■
C11
SETPOINT
G11
FILTER GROUND
C12
+32 VDC
G12
SAFETY GROUND
LOGIC INPUTS
CT and VT INPUTS / POWER
D1
LOGIC INPUT 8
H1
COIL MONITOR 1 -
D2
LOGIC INPUT 9
H2
COIL MONITOR 2 -
D3
LOGIC INPUT 10
H3
SENSITIVE GROUND CT
D4
LOGIC INPUT 11
H4
SYNCHRO VT
(LINE)
D5
LOGIC INPUT 12
H5
PHASE B VT
■
(BUS)
D6
LOGIC INPUT 13
H6
PHASE VT NEUTRAL
(BUS)
D7
LOGIC INPUT 14
H7
PHASE A CT
D8
RESERVED
H8
PHASE B CT
D9
RESERVED
H9
PHASE C CT
D10
RESERVED
H10
GROUND CT
D11
RESERVED
H11
CONTROL POWER -
D12
DC NEGATIVE
H12
CONTROL POWER +
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...