16-
56
750/760 Feeder Management Relay
GE Power Management
16.4 MODBUS MEMORY MAP
16 COMMUNICATIONS
16
S7
RECLOSURE SHOT 4 - 760 ONLY
READ/WRITE
1BF0
2
Deadtime Before Reclosure 4
0.00 to 300.00
s
F3
5.00 s
1BF1
1
Select Setpoint Group
---
---
F80
Active Group
1BF2
2
Overcurrent Blocking Flags
---
---
F59
None blocked
1BF3
1
Phase Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BF4
1
Neutral Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BF5
1
Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
1BF6
1
N ega tive S e que nce Tim e O vercu rre nt R aised P ickup
0 to 100
%
F1
0%
1BF7
3
Sensitive Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
S3
LOGIC INPUTS NAMES
READ/WRITE
1C00
1
Logic Input 1 Name (9 words = 18 characters)
---
---
F33
Logic Input 1
1C09
1
Logic Input 2 Name (9 words = 18 characters)
---
---
F33
Logic Input 2
:
:
:
:
:
:
1CAB
1
Logic Input 20 Name (9 words = 18 characters)
---
---
F33
Logic Input 20
A4
EVENT RECORD SELECTOR
READ/WRITE
2000
Event Number Selector
0 to 65535
---
F1
0
A4
EVENT RECORDOR INFORMATION
READ ONLY
2001
Number of Events Since Clear
0 to 65535
---
F1
0
2002
Event Recorder Last Cleared (2 words)
---
---
F23
---
A4
EVENT RECORD DATA
READ ONLY
2010
Record #N Date of Event (2 words)
---
---
F23
---
2012
Record #N Time of Event (2 words)
---
---
F22
---
2014
Record #N Cause of Event
---
---
F24
---
2015
Record #N Phase A Current Magnitude
0 to 65535
A
F1
---
2016
Record #N Phase B Current Magnitude
0 to 65535
A
F1
---
2017
Record #N Phase C Current Magnitude
0 to 65535
A
F1
---
2018
Record #N Ground Current Magnitude
0 to 65535
A
F1
---
2019
Record #N A-N (A-B) Voltage Magnitude
0.00 to 600.00
kV
F3
---
201A
Record #N B-N (B-C) Voltage Magnitude
0.00 to 600.00
kV
F3
---
201B
Record #N C-N (C-A) Voltage Magnitude
0.00 to 600.00
kV
F3
---
201C
Record #N System Frequency
0.00 to 90.00
Hz
F3
---
201D
Record #N Analog Input
0 to 65535
Units
F1
---
201E
1
Record #N Phase A Current Angle
0 to 359
°
Lag
F1
---
201F
1
Record #N Phase B Current Angle
0 to 359
°
Lag
F1
---
2020
1
Record #N Phase C Current Angle
0 to 359
°
Lag
F1
---
Table 16–15: MODBUS MEMORY MAP (Sheet 39 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...