GE Power Management
750/760 Feeder Management Relay
10-
3
10 S3 LOGIC INPUTS
10.2 LOGIC INPUTS SETUP
10
10.2.2 SETTINGS
■
LOGIC INPUTS SETUP
■
[ENTER] for more
The Logic Inputs Setup setpoints path is:
\ SETPOINTS \ S3 LOGIC INPUTS \ LOGIC INPUTS SETUP
INPUT 1 NAME:
Logic Input 1
Range: Any Combination of 18 Alphanumeric Characters.
An 18 character field that will be displayed in the
ACTUAL VALUES \ A1 STATUS \
VIRTUAL INPUTS
menu. This allows a more operator friendly description to be
used when replacing panel switches with a virtual switch.
LOGIC 1 ASSERTED
LOGIC: Contact Close
Range: See below.
This setpoint determines how to combine the state of the contact and virtual
input to determine the state of the logic input.
For logic inputs 1 to 14 the setpoint has the following choices:
For logic inputs 15 to 20 the setpoint has the following choices:
SETPOINT VALUE
LOGIC INPUT ASSERTED WHEN:
Disabled
Never
Contact Close
Contact is closed
Contact Open
Contact is open
Virtual On
Virtual input is on
Virtual Off
Virtual input is off
Closed & Von
Contact is closed AND virtual input is on
Closed & Voff
Contact is closed AND virtual input is off
Open & Von
Contact is open AND virtual input is on
Open & Voff
Contact is open AND virtual input is off
Closed | Von
Contact is closed OR virtual input is on
Closed | Voff
Contact is closed OR virtual input is off
Open | Von
Contact is open OR virtual input is on
Open | Voff
Contact is open OR virtual input is off
Closed X Von
Contact is closed XOR virtual input is on
Closed X Voff
Contact is closed XOR virtual input is off
Open X Von
Contact is open XOR virtual input is on
Open X Voff
Contact is open XOR virtual input is off
SETPOINT VALUE
LOGIC INPUT ASSERTED WHEN:
Disabled
Never
Virtual On
Virtual Input is On
Virtual Off
Virtual Input is Off
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...