GE Power Management
750/760 Feeder Management Relay
16-
25
16 COMMUNICATIONS
16.4 MODBUS MEMORY MAP
16
A2
CURRENT PHASE ANGLES
READ ONLY
0400
Phase A Current Angle
0 to 359
°
Lag
F1
---
0401
Phase B Current Angle
0 to 359
°
Lag
F1
---
0402
Phase C Current Angle
0 to 359
°
Lag
F1
---
0403
Neutral Current Angle
0 to 359
°
Lag
F1
---
0404
Ground Current Angle
0 to 359
°
Lag
F1
---
0405
3
Reserved Polarizing Current Angle
---
---
---
---
0406
3
Sensitive Ground Current Angle
0 to 359
°
Lag
F1
---
A2
VOLTAGE PHASE ANGLES
READ ONLY
0410
A-N Voltage Angle
0 to 359
°
Lag
F1
---
0411
B-N Voltage Angle
0 to 359
°
Lag
F1
---
0412
C-N Voltage Angle
0 to 359
°
Lag
F1
---
0413
A-B Voltage Angle
0 to 359
°
Lag
F1
---
0414
B-C Voltage Angle
0 to 359
°
Lag
F1
---
0415
C-A Voltage Angle
0 to 359
°
Lag
F1
---
0416
5
Neutral Voltage Angle
0 to 359
°
Lag
F1
---
A2
SYMMETRICAL COMPONENTS
READ ONLY
0420
Positive Sequence Current Magnitude
0 to 65535
A
F1
---
0421
Positive Sequence Current Angle
0 to 359
°
Lag
F1
---
0422
Negative Sequence Current Magnitude
0 to 65535
A
F1
---
0423
Negative Sequence Current Angle
0 to 359
°
Lag
F1
---
0424
Zero Sequence Current Magnitude
0 to 65535
A
F1
---
0425
Zero Sequence Current Angle
0 to 359
°
Lag
F1
---
0426
Positive Sequence Voltage Magnitude
0.00 to 600.00
kV
F3
---
0427
Positive Sequence Voltage Angle
0 to 359
°
Lag
F1
---
0428
Negative Sequence Voltage Magnitude
0.00 to 600.00
kV
F3
---
0429
Negative Sequence Voltage Angle
0 to 359
°
Lag
F1
---
042A
Zero Sequence Voltage Magnitude
0.00 to 600.00
kV
F3
---
042B
Zero Sequence Voltage Angle
0 to 359
°
Lag
F1
---
PROTECTION FUNCTION STATES
READ ONLY
0600
Reserved
0601
2
Phase Time Overcurrent 1
---
---
F49
---
0602
2
Phase Instantaneous Overcurrent 1
---
---
F49
---
0603
2
Phase Instantaneous Overcurrent 2
---
---
F49
---
0604
2
Ground Time Overcurrent
---
---
F49
---
0605
2
Ground Instantaneous Overcurrent
---
---
F49
---
Table 16–15: MODBUS MEMORY MAP (Sheet 8 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Summary of Contents for 750
Page 2: ......
Page 4: ......
Page 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Page 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Page 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...