16-
98
750/760 Feeder Management Relay
GE Power Management
16.5 DNP 3.0 DEVICE PROFILE
16 COMMUNICATIONS
16
When “Enabled”, the User Map Values are assigned to points 0 through 119 with the preassigned Analog Outputs fol-
lowing beginning with point index 120. The value read from points 0 through 119 will depend upon the value pro-
grammed into the corresponding User Map Address setpoint (note that programming of these setpoints can only be
accomplished via Modbus). Refer to Section 16.3.15: ACCESSING DATA VIA THE USER MAP on page 16–16 for
more information.
Please note that changes in User Map Values never generate event objects.