6. SYSTEM DESIGN
SEPARATION TUBE
3-2.
PIPE CONNECTION
CAUTION
Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is improper,
●
the flare nut cannot be tighten smoothly. If the flare nut is forced to turn, the threads will be
damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before connecting the
●
connection pipe.
Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to tighten the
●
flare nut correctly.
Tighten the flare nuts with a torque wrench using the specified tightening method. Otherwise,
●
the flare nuts could break after a prolonged period, causing refrigerant to leak and generate a
hazardous gas if the refrigerant comes into contact with a flame.
When the flare nut is tightened properly by your hand, hold the body side coupling with a separate
spanner, then tighten with a torque wrench. (See the table below for the flare nut tightening torques.)
Flare nut
[mm (in.)]
Tightening torque
[N·m (lbf· ft)]
6.35 (1/4)
16 to 18 (11.8 to 13.3)
9.52 (3/8)
32 to 42 (23.6 to 31.0)
12.70 (1/2)
49 to 61 (36.1 to 45.0)
15.88 (5/8)
63 to 75 (46.5 to 55.3)
19.05 (3/4)
90 to 110 (66.4 to 81.1)
Type of separation tube
Name and shape
Liquid pipe
Gas pipe
Positioning of separation tube
CAUTION
If it is placed horizontally, keep it within ± 15°. Otherwise, it will not separate the refrigerant evenly,
●
causing a reduction in performance.
Place the separation tube in a horizontal position as far as possible. Only place the separation
●
tube as shown below during unavoidable circumstances.
A
B
A
B
A
B
±15°
Horizontal
OK
A: Outdoor unit or Separation tube
B: Branch box or Separation tube
OK
OK
Not good
Not good
Horizontal
line
Vertical
or
- (06 - 29) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...