6. SYSTEM DESIGN
Limitation check
Diagram
Example
ft (m)
Limitation
ft (m)
Judge
Total pipe length
Total
234
(72)
Less than 377 (115)
OK
Between outdoor unit and the farthest indoor unit
a + c + k
121
(37)
Less than 230 (70)
OK
Between outdoor unit and branch boxes
a + c + d
138
(42)
Less than 180 (55)
OK
Between branch box and indoor unit
Total
f + g + h + i + j + k
96
(30)
Less than 197 (60)
OK
Each unit
f, g, h, i, j, k
16
(5)
Between 10 to 49
(3 to 15)
OK
Between outdoor unit and the first separation tube
a
23
(7)
Greater than 16 (5)
OK
Calculation of additional charge refrigerant
Liquid pipe size
in. (mm)
1/4
(6.35)
3/8
(9.52)
Additional refrigerant
oz./ft. (g/m)
0.224
(21)
0.624
(58)
Liquid pipe length
ft (m)
96
(30)
138
(42)
Additional charge = (0.224 x 96) + (0.624 x 138) = 107.62 oz. = 6.73 lbs
[Additional charge = (21 x 30) + (58 x 42) = 3066 g = 3.07 kg]
- (06 - 21) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...