6. SYSTEM DESIGN
PIPING DESIGN
2.
IMPORTANT ITEMS WHEN USING NEW REFRIGERANT
2-1.
(R410A)
R410A operates at higher pressure and has less solubility with mineral oil than
traditional R22 refrigerant. Therefore, the lubricant and a part of pipe material are different.
Some special tools are necessary.
REFRIGERANT PIPING MATERIAL AND WALL THICKNESS
It is necessary to use seamless copper tubes for refrigerant use.
Thickness of tubes are shown in table below.
Endurance pressure of the pipe must be 609 psi (4.2 MPa).
Nominal Diameter
(in)
1/4"
3/8"
1/2"
5/8"
3/4"
Outside Diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Material
JIS H3300 C1220T-O or equivalent *1
Wall Thickness *2
(mm)
0.8
0.8
0.8
1.0
1.2
*1: Allowable tensile stress ≥ 33 (N/mm
2
)
*2: Endurance pressure of the pipe must be 609 psi (4.2 MPa).
Please select the pipe size in accordance with local rules.
LUBRICANT
Refrigerant
R410A (Mixed refrigerant)
Lubricant
Synthetic oil
TOOLS
R410A work requires a number of special tools. Since the tools (with *4 symbol) for R22 work
cannot be used for R410A, prepare them beforehand.
Tool name
Process and application
Pipe cutter
Pipe cutting
Refrigerant piping work
Flaring tool *4
Pipe flaring work
Torque wrench *4
Flare nut connection
Expander
Expansion at pipe connection
Pipe bender
Pipe bending work
Nitrogen gas
Pipe interior oxidation prevention
Air tightness test
Welder
Pipe brazing
Gauge manifold *4
Vacuum evacuation and refrigerant
charging Operation check
Air tightness test ~
Refrigerant additional charging
Charging hose *4
Vacuum pump (with adaptor) *4
Vacuum drying
Electronic scale for refrigerant charging
Refrigerant additional charging
Gas leak tester *4
Gas leakage test
*4: Please refer to a service manual for details.
- (06 - 10) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...