6. SYSTEM DESIGN
EXTERNAL OUTPUT
7-2-2.
OPERATION STATUS OUTPUT
Compact Cassette
Slim Duct
Comapct Wall
Mounted
Wall Mounted
Connector
CN103
CN103
CN304
CN16
An air conditioner operation status signal can be output.
Circuit diagram example
Relay spec.:
Max.24V DC, 10mA to less
than 500mA.
Field supply
Ex.)Display
Indoor unit
control PC board *1
Connected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
33ft. (10m)
*2
24V DC
*1: PC board of Communication kit is used for Compact wall mounted type.
*2: Make the distance from the PC board to the connected unit within 33ft. (10m).
ON
OFF
Operation
Stop
Indoor unit
Output signal
Parts (Optional)
Compact Cassette
Slim Duct
Compact Wall Mounted
Wall Mounted
Parts name
External connect kit
Model name
UTY-XWZX
Compact Cassette
Slim Duct
Compact Wall
Mounted
Wall Mounted
Parts name
-
-
Communication kit
-
Model name
-
-
UTY-XCBXZ1
-
* For operating the EXTERNAL OUTPUT function, the Compact wall mounted type requires the communication kit
(UTY-XCBXZ1) in addition to the wire (UTY-XWZX).
- (06 - 101) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...