6. SYSTEM DESIGN
INDOOR UNIT
For the air conditioner to operate satisfactorily, install it as outlined in installation manual.
Indoor unit mounting position
Decide the mounting position with the customer
●
Install the unit level on a strong wall, floor, ceiling which is not subject to vibration.
●
The inlet and outlet ports should not be obstructed. The air should be able to blow all over the
●
room.
Install the unit where the connection pipe can be easily installed.
●
Install the unit where the drain pipe can be easily installed.
●
Take servicing, etc. into consideration and leave the spaces. Also install the unit where the
●
filter can be removed.
Install the unit where satisfy the pipe length and height.
●
Indoor unit mounting limitation
Install at a place that can withstand the weight of the indoor unit and install positively so that
●
the unit will not topple or fall.
Do not install the unit where there is the danger of combustible gas leakage.
●
Do not install the unit near heat sources and the location with high temperature.
●
Do not install the unit near a source of heat, steam, or flammable gas.
●
Do not use the unit for air conditioning or saving precision instrument, food, art, plants and
●
animal as special place.
If children may approach the unit, take preventive measures so that they cannot reach the
●
unit.
Do not install where there is oily smoke, machine oil (i.e. factory), salty environment with
●
direct sea breeze, and too much of dust.
Install the unit where drainage does not cause any trouble.
●
Control may not operate correctly if the unit is installed near machinery which emit
●
electromagnetic wave.
Install the unit in a well-ventilated place avoiding rains and direct sunlight.
●
Install the unit where air from the outlet and noise do not disturb the neighbour.
●
Install the indoor and outdoor units, power wiring, signal wiring and remote control wiring 3ft.
●
(1m) away from television and radio to avoid distorted images and noise. (However, distorted
noise may not be avoidable even if units and wiring mentioned above are installed 3ft. (1m)
away from television and radio depending on conditions of electromagnetic disturbance.)
When installing an indoor unit in a small room, a countermeasure must be taken to keep
●
refrigerant concentration limitations will never be exceeded even if there is a refrigerant leak.
BRANCH BOX
Install the unit in a location such as above the ceiling or on the wall surface, following the
conditions below.
The branch box is for indoor installation only.
●
Install the branch box in a location that has strong support and no vibrations.
●
Install in a location that is not close to any heat or steam source.
●
Install in a location that has enough space for branch box installation.
●
Install in a location that is not exposed to high temperatures or humidity over a long periods.
●
Install in a well-ventilated area.
●
Do not install the unit near a bedroom. Refrigerant noise may be heard from the piping.
●
- (06 - 09) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...