4. INDOOR UNITS
WALL MOUNTED TYPE
2-4.
Model name
ASU18RLF
ASU24RLF
Power source
1ø 208/230V 60Hz
Available voltage range
187-264V
Capacity
Cooling Rated
Btu/h
18,000 24,000
kW
5.28 7.02
Heating Rated
Btu/h
20,000 27,000
kW
5.85 7.92
Moisture removal
pints/h(l/h)
5.3 (2.5)
5.9 (2.8)
Power consumption
W
41
69
Running current
A
0.32
0.53
Fan
Airflow
rate
Cooling
High
CFM
(m
3
/h)
542 (920)
659 (1120)
Med
436 (740)
530 (900)
Low
365 (620)
436 (740)
Quiet
324 (550)
365 (620)
Heating
High
542 (920)
647 (1100)
Med
436 (740)
530 (900)
Low
365 (620)
436 (740)
Quiet
324 (550)
365 (620)
Fan type × Q'ty
Cross flow ×1
Fan motor output
W
64
64
Sound pressure level
Cooling
High
dB(A)
43
49
Med
37
42
Low
33
37
Quiet
31
33
Heating
High
44
48
Med
37
42
Low
33
37
Quiet
31
33
Heat
exchanger
Dimension (H×W×D)
in.(mm)
Main:15-7/8 x 33-3/4 x 1-1/16 (378 x 832 x 26.6)
Sub:3-5/16 x 33-3/4 x 17/32 (84 x 832 x 13.3)
Fin pitch
FPI
Main:21, Sub:18
Rows × Stages
Main:2 x 18, Sub:1 x 4
Pipe type
Copper tube
Fin Type
Aluminium
Enclosure
Material
Polystyrene
Color
White
(Approximate color of Mansell N9.25 /)
Dimensions
( H×W ×D )
Net
mm
12-5/8 x 39-1/4 x 9 (320×998×228)
Gross
12-9/16 x 42-15/16 x 16-7/8 (319×1090×429)
Weight
Net
lb.(kg)
31 (14)
31 (14)
Gross
40 (18)
40 (18)
Connection
pipe
Size
Liquid
in.(mm)
1/4 (6.35)
Gas
1/2 (12.7)
5/8 (15.88)
Method
Flare
Drain pipe
Material
PVC
size
in.(mm)
Outer diameter : 5/8 (16)
Inner diameter : 15/32 (12)
Operation range
Cooling
°F (°C)
64 to 90 (18 to 32)
%RH
80 or less
Heating
°F (°C)
60 to 88 (16 to 31)
Remote controller type
Wireless [Wired(option)]
Note : Specifications are based on the following conditions.
Power source of specifications : 230V
Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB.
Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB.
Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit]
Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].
- (04 - 08) -
INDOOR
UNITS
INDOOR
UNITS
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...