6. SYSTEM DESIGN
INDOOR UNIT (setting by wireless remote controller)
5-3.
This procedure changes to the function settings used to control the indoor unit according to
●
the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the
●
installation conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting
●
Number.
Settings will not be changed if invalid numbers or setting numbers are selected.
●
PREPARATION
(1) Turn on the power to the Branch box.
By turning on the power indoor units, so make sure the piping air-tight test and vacuuming have been
conducted before turning on the power.
Also check again to make sure no wiring mistakes were made before turning on the power.
Indoor
units
Branch box
Breaker ON
- (06 - 55) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...