6. SYSTEM DESIGN
[Installation precautions]
Contents
Countermeasures (Reference)
When
installation
environment is
quiet
When the wall mounting type was installed
in a bedroom, living room, or other quiet
place, the sound of the refrigerant flow may
be sensed as noise and must be taken into
accunt.
1) Plan installation of a branch
box farther from indoor
unit.
2) Plan installation using
another air conditioner.
When
installing duct
type in ceiling
chamber
system
In the case of the ceiling chamber system
(duct is not installed at indoor unit inlet
side and room air is sucked into the indoor
unit through the inside of the ceiling), the
thermistor inside the indoor unit may not
correctly detect the room temperature.
Heating operation: Room is not heated
because the indoor unit is easily turned off by
the thermostat.
Cooling operation: Room is too cold because
the indoor unit is difficult to turn off by the
thermostat.
1) Replace the indoor unit
thermistor with a Remote
sensor unit (optional
parts) and install the
sensor where the room
temperature can be
correctly detected
When the
outlet air is
sucked in at
duct type
Cooling operation does not cool the room
and heating operation does not heat the room
because the short circuited indoor unit is not
turned on by the thermostat.
1) Reconsider the ventilation
port construction
2) Replace the indoor unit
thermistor with a Remote
sensor unit (optional
parts) and install the
sensor where the room
temperature can be
correctly detected.
- (06 - 131) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...